Network configuration of the inverter without EDS file

The cyclic data transfer (Implicit Messaging) without EDS file is set up in 4 steps.
 
Step 1 - Set up a new Ethernet device:
1.
Go to the "Controller Organizer" under "I/O Configuration" 
à
"Ethernet" and execute the menu command "New Module" with a right-click.
 
2.
Select the "ETHERNET MODULE Generic Ethernet Module" module type in the dialog box.
 
3.
Click "Create".
The "New Module" dialog box is opened.
 
4.
Fill in input fields.
The example shows the configuration for the Lenze standard technology application "Speed Control". 0x4000 = 10
The assembly input object 135 is used for reading status information of the inverter and the assembly output object 134 is used for controlling the inverter.
If another technology application is used, the assigned assembly objects must be used: 0x04-Assembly Object 
 
 
a.
"Name:" The name to be entered should refer to the process or the device. Select
 
b.
"Comm Format:" Data - DINT because the data in assembly objects are available in 32-bit integer words.
 
c.
"IP Address:" The inverter (adapter) must be in the same subnetwork as the PLC (scanner). The subnetwork corresponds to the first 3 bytes of the IP address. Basic setting and options 
 
d.
Enter "Connection Parameters":
"Input:" Assembly Instance = 135, Size = 8
"Output:"Assembly Instance = 134, Size = 8
"Configuration:"Assembly Instance = 130, Size = 16
 
5.
Click "OK".
The "Module Properties Report: ..." dialog box is opened.
 
 
Step 2 - Set up connection:
1.
Click the "Module Properties Report: ..." tab in the "Connection" dialog box.
 
2.
Set "Requested Packet Interval (RPI)" (cycle with which the inverter is scanned by the scanner).
The default setting is 10.0 ms. For most applications, it is not necessary to scan the inverter more frequently.
The minimum value is 1.0 ms.
 
 
3.
Select connection type: "Unicast" or "Multicast“.
For this purpose, activate/deactivate "Use Unicast Connection over EtherNet/IP".
 
4.
Optional settings:
 
a.
"Inhibit Module": Activate locks the inverter.
 
b.
"Major Fault On Controller If Connection Fails While in Run Mode": Activate switches the inverter to "Error" if the EtherNet/IP connection to the inverter is lost during operation.
 
5.
Assembly tags are created in the "Controller Organizer" under "Controller" 
à
 "Controller Tags".
 
6.
Click "OK".
In the sample configuration with the "LenzeServo1" inverter, these three assembly tags are generated:
"LenzeServo1:C" for the configuration assembly
"LenzeServo1:I" for the input assembly
"LenzeServo1:O" for the output assembly
Clicking the icon in front of the assembly names expands the display of the assemblies.
 
 
Step 3 - Create alias tags for individual bits of the assemblies:
1.
Go to "Controller Organizer" under "Controller" and open the "Controller Tags".
 
2.
Right-click any tag to execute the "New Tag" context menu command.
The "New Tag" dialog box is opened.
 
3.
Fill in input fields (example):
 
a.
"Name:" Enter the name for the alias tag, e.g. "i950_Contr_Rel".
 
b.
Select "Type:" "Alias".
 
c.
"Alias For:" Select the assembly tag. e.g. assign the double word 0 (LenzeServo1:O.Data[0]) to the alias "i950_Contr_Rel" in the output assembly.
 
4.
Click "Create".
The new alias tag is added to the database.
 
5.
If necessary, create additional alias tags.
 
The network configuration of the inverter is now complete.
 
Step 3 - Save configuration:
1.
Save the "RSLogix™" project and load the configuration into the PLC (scanner).
Save »RSLogix™« project/Load configuration into the Scanner 
 
The configuration without the EDS file is now complete.
 
Example for an output assembly
Example: Display of the 8 double words of the output assembly "LenzeServo1:O":