External torque limits
An external torque limit is defined via the External torque limit parameter.
0x5030:017
0x5030:017The external torque limit is activated with bit 31 of the Control signal parameter.
0x5030:010
0x5030:010Bit 31 of the Status signals parameter indicates whether the external torque limit is active.
0x5030:110
0x5030:110As long as the external torque limit remains inactive, the two parameters Positive torque limit and Negative torque limit define what torque limits apply.
0x500A:128
0x500A:129
0x500A:128
0x500A:129The function mode of the external torque limit is set via the Impact of external speed limit parameter.
0x5030:003
0x5030:003The following settings are possible via this parameter:
0x5030:003 = 0: Setting affects the positive and negative torque limit
0x5030:003 = 1: Setting affects the positive torque limit
0x5030:003 = 2: Setting affects the negative torque limit
Static torque limits can be defined for the axis, which are active during normal operation. The definition is done via the parameters:
The torque limits can be deactivated in the technology application and can be replaced by alternative torque limits.
The alternative torque limits are set in the technology application via a control word
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
If the set torque limits in the technology application have been changed, this is indicated in the Status word parameter in bit 20.
0x500A:005 Bit 20
0x500A:005 Bit 20 The torque limits currently effective in the drive are displayed in the parameters Positive torque limit source and Negative torque limit source.
0x60E0
0x60E1
0x60E0
0x60E1 Parameter