Controller.Firewall : PortList with activated firewall and default parameter set
The following table shows the ports, scanned with nmap -sT (TCP connect scan) with activated Controller.Firewall and a default parameter set.
Open TCP Ports with activated Controller.Firewall and default parameter set
|
Port |
Engineering Port X16 |
PROFINET Device*1) |
Ethernet Switch*3) |
Protocol |
|---|---|---|---|---|
|
22/tcp |
þopen*3) |
ofiltered |
ofiltered |
|
|
80/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
443/tcp |
þopen |
ofiltered |
ofiltered |
|
|
1217/tcp |
þopen |
ofiltered |
ofiltered |
|
|
4840/tcp |
þopen |
ofiltered |
þopen |
|
|
6000/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
7100/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
7200/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
8080/tcp |
ofiltered*5) |
ofiltered |
ofiltered |
Web Visu Server (only available for the extended Controller variant) |
|
9410/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
11740/tcp |
þopen |
ofiltered |
ofiltered |
|
|
31855/tcp |
ofiltered |
ofiltered |
ofiltered |
|
|
47877/tcp |
ofiltered |
ofiltered |
ofiltered |
*1) ProfiNET Device via ProfiNET IO-Device module with X256/X257 for c5x0 controller and via onboard network with X396/X397 for c430 controller.
*2) Ethernet switch not available for c5x0 controller and via onboard network with X396/397 for c430 controller.
*3) For more information please refer to chapter Controller.SSHServer: Combination of SSH and SFTP via Ports and Networks
*4) Port 6000/tcp is only open if the application contains an EtherCAT-master object.
*5) Port 8080/tcp is only open if the ‘Extended for customer specific devices only’ variant of the Controller is used and will be filtered if the firewall with default parameter is activated.
The following table shows the ports, scanned with nmap -sU (UDP scan) with activated Controller.Firewall and default parameter set.
Open UDP ports with activated Controller.Firewall and default parameter set
|
Port |
Engineering Port X16 |
PROFINET Device*1) |
Ethernet Switch*2) |
Protocol |
|---|---|---|---|---|
|
68/udp |
oopen|filtered |
oopen|filtered |
oopen|filtered |
DHCP Client |
|
123/udp |
oopen|filtered |
oopen|filtered |
oopen|filtered |
|
|
161/udp |
oopen|filtered |
þopen |
oopen|filtered |
SNMP |
|
1740/udp 1741/udp 1742/udp 1743/udp |
þopen|filtered oclosed oclosed oclosed*3) |
þopen|filtered þopen|filtered þopen|filtered þopen|filtered*3) |
oopen|filtered oopen|filtered oopen|filtered oopen|filtered*3) |
|
|
3677/udp |
oopen|filtered |
oopen|filtered |
oopen|filtered |
ESDCP |
|
4840/udp |
oopen|filtered |
oopen|filtered |
oopen|filtered |
*1) ProfiNET Device via ProfiNET IO-Device module with X256/X257 for c5x0 Controller and via onboard network with X396/X397 for c430 Controller.
*2) Ethernet Switch not available for c5x0 Controller and via onboard network with X396/397 for c430 Controller.
*3) Due to the scanning properties of nmap for UDP ports, these UDP ports are displayed as ‘open|filtered’. However, UDP communication can only take place via the engineering port and Ethernet Switch and not via PROFINET.