Controller.Firewall : PortList with deactivate firewall

Port List with deactivated firewall

The following table shows the ports, scanned with nmap -sT (TCP connect scan) without activated Controller.Firewall.

Open TCP Ports with deactivated Controller.Firewall

Port

Engineering Port X16

PROFINET Device*1)

Ethernet Switch*2)

Protocol

22/tcp

þopen*3)

ofiltered

þopen*3)

Secure Shell (SSH)

80/tcp

þopen

ofiltered

þopen

Hypertext Transfer Protocol (HTTP)

443/tcp

þopen

þopen

þopen

Secure Hypertext Transfer Protocol (HTTPS)

1217/tcp

þopen

ofiltered

þopen

PLC-Designer TCP Gateway-Search

4840/tcp

þopen

þopen

þopen

Lenze OPC-UA Server

6000/tcp

þopen*4)

ofiltered

oclosed

EtherCAT Master Diagnosis

7100/tcp

þopen

ofiltered

þopen

UI-Designer RAW

7200/tcp

þopen

þopen

þopen

UI-Designer secure-RAW

8080/tcp

þopen*5)

ofiltered

þopen*5)

Web Visu Server (only available for the extended Controller variant)

11740/tcp

þopen

þopen

þopen

PLC-Designer Gateway

31855/tcp

þopen*3)

ofiltered

þopen*3)

SFTP (SSH File Transfer Protocol)

47877/tcp

þopen*3)

þopen*3)

þopen*3)

SFTP (SSH File Transfer Protocol)

*1) ProfiNET Device via ProfiNET IO-Device module with X256/X257 for c5x0 controller and via onboard network with X396/X397 for c430 controller.

*2) Ethernet switch not available for c5x0 Controller and via onboard network with X396/397 for c430 controller.

*3) For more information please refer chapter Controller.SSHServer: Combination of SSH and SFTP via ports and networks

*4) Port 6000/tcp is only open if the application contains an EtherCAT-master object.

*5) Port 8080/tcp is only open if the ‘Extended for customer specific devices only’ variant of the controller is used and will be filtered if the firewall with default parameter is activated.

The following table shows the ports, scanned with nmap -sU (UDP scan) with activated Controller.Firewall and default parameter set.

Open UDP Ports with activated Controller.Firewall

Port

Engineering Port X16

PROFINET Device*1)

Ethernet Switch*2)

Protocol

68/udp

oopen|filtered

oopen|filtered

oopen|filtered

DHCP Client

123/udp

þopen *4)

oopen|filtered

þopen *4)

NTP Client and Server

161/udp

oclosed

þopen

oclosed

SNMP

1740/udp

1741/udp

1742/udp

1743/udp

þopen|filtered

oclosed

oclosed

oclosed*3)

oopen|filtered

oopen|filtered

oopen|filtered

oopen|filtered*3)

þopen|filtered

oclosed

oclosed

oclosed*3)

PLC-Designer UDP Communication

3677/udp

oopen|filtered

oopen|filtered

oopen|filtered

ESDCP

4840/udp

þopen *5)

þopen *5)

þopen *5)

Lenze OPC-UA PubSub

*1) ProfiNET Device via ProfiNET IO-Device module with X256/X257 for c5x0 controller and via onboard network with X396/X397 for c430 controller.

*2) Ethernet switch not available for c5x0 controller and via onboard network with X396/397 for c430 controller.

*3) Due to the scanning properties of nmap for UDP ports, these UDP ports are displayed as ‘open|filtered’. However, UDP communication can only take place via the engineering port and Ethernet switch and not via PPROFINET.

*4) UDP port available if NTP server is activated with parameter 0x245B:003 = Activated [1].

*5) UDP port available if OPC-UA is configured with the feature publisher / subscriber.