The Alarms system module
The purpose of an HMI is to display machine states. This basic HMI concept is extended by an alarm system through the following features:
-
Machine states can be displayed by a single control element.
-
The presentation can be filtered and preprocessed (e.g. by priority and group).
-
Machine states can be acknowledged by the user.
-
Machine states and their acknowledgements can be archived.
Alarm
Alarms are special definitions contained in the project file.
The purpose of alarms is to:
-
display and archive disturbances and their acknowledgements,
-
collect production data.
An alarm consists of a unique name and a set of parameters. A unique name ensures the traceability of an alarm’s origin. The parameters describe the alarm-specific properties.
Alarm group
The Alarms system module makes it easy to create alarm names by grouping alarms: Alarm groups have the same function as folders in a file system—they organize alarms. Alarm names must only be unique within a folder (i.e. alarm group). In addition, alarm groups allow to create machine component based projects. Alarm groups support developers and users in identifying error sources and provide for an easier exchange of HMI components. Alarm groups also function as a collective alarm. All alarms that are contained in an alarm group can be displayed and acknowledged together as a collective alarm.
Alarm class
The Alarms system module also includes alarm classes. Alarm classes are templates for alarm parameters. The alarm classes determine the behavior of alarms with regard to their style and acknowledge mode. Alarm classes help the developer: Instead of setting the same parameter options again and again, you can make a reference to a combination of parameters by setting a single alarm parameter (Alarm class parameter).
Alarm type
Alarm types have a similar purpose: They serve as templates that determine alarm behavior with regard to trigger variables. Basically, alarms are triggered by a change in the process variable value. Alarm types describe how the system interprets such changes:
-
Simple bit alarm (without a reference to an alarm type)
-
The alarm definition specifies the event variable, the triggering bit and other alarm information (text, acknowledge mode, etc.). If the triggering bit is set at runtime, the Alarms system triggers the alarm and displays the corresponding alarm information.
-
-
Bit block alarm type
-
The event variable is indicated in the alarm definition. The definition contains a reference to a bit block alarm type within which a set of alarm information is assigned to each bit of the event variable. At runtime, the alarm is triggered if the corresponding bit of the process variable is set.
-
-
Numerical alarm type
-
Within a numerical alarm type, a set of alarm information is assigned to numeric values. The alarm definition contains the event variable and a reference to the numerical alarm type. If at runtime the event variable assumes one of the values defined in the alarm type, the corresponding alarm information is displayed.
-
Related topics: