Configure setpoint sources

The standard setpoint source for torque control can be selected in 0x2860:003 (P201.03). This chapter describes the setting options for the various setpoint sources.
 
–
Preset torque setpoint source: Analog input 1. Set the setting range in 0x2636:011 (P430.11) and 0x2636:012 (P430.12) in this selection.
 
–
In case of selection "Analog input 2 [3]": Set setting range in 0x2637:011 (P431.11) and 0x2637:012 (P431.12).
 
–
Except for the network, the torque setpoint must be specified in percent with regard to the rated motor torque configured in 0x6076 (P325.00).
 
–
Via the network, the torque setpoint is specified via the mappable parameter 0x400B:008 (P592.08) in [Nm / 2scaling factor]. The scaling factor can be set in 0x400B:009 (P592.09).
 
–
Corresponding functions make it possible to change over to other setpoint sources during operation. More detailed information on this can be found in the chapter "Configuring frequency control":Changing the setpoint source during operation 
 
 
The following setpoint sources are described in this chapter:
–
 
–
 
–
 
 
Setpoint sources described in other chapters:
–
 
–
 
–
 
–