Suppress diagnostic messages to the IO controller

Inverter errors and warnings are sent to the IO controller as alarm messages. This function is used to suppress, for example, the fact that the "undervoltage DC link" warning triggers an alarm and the associated control switches to the stop mode if there is no associated alarm block or has been programmed manually. It should be noted here, that an alarm block not programmed in the control can pose risks to the machine. A reduction of possible alarm messages initially helps when the machine is commissioned. Later on, however, more effort should be made to program the alarm blocks.
 
Please note that an unprogrammed alarm block in the IO controller can pose risks to the machine. A reduction of possible alarm messages initially helps when the machine is commissioned. Later on, however, more effort should be made to program the alarm blocks.
 
 
0x285A:001 serves to set which error response in the device suppresses the alarm message to the IO-Controller.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x285A:001
Diagnostic configuration: Alarm suppression
0 ... [0] ... 65535
–
From version 05.01
 
Bit coded selection of error responses which suppress the alarm message to the IO controller.
–
Bit x = 1 = suppress alarm message.
 
–
In the default setting "0", an alarm message is displayed for all error responses.
 
Bit 0
Information
Bit 1
Warning
Bit 3
Trouble
Bit 7
Fault > inverter disabled