Basic setting and options

Addressing the EtherCAT devices
The EtherCAT devices are normally addressed via a permanent 16-bit address defined by the master. At the start, this address is assigned automatically to each node by the master, depending on the physical order in the network. The address is not saved and gets lost when the device is switched off.
 
"Explicit Device Identification" via rotary encoder switch or parameter
"Explicit Device Identification" is required if the device is part of a "Hot Connect" group or the device is operated within a modular Lenze machine application. Each slave receives an unambiguous identifier for being identified by the master.
Setting
Assignment of the identifier
0x00
Identifier via the parameter 0x2361:004 (P510.04).
0x01 ... 0xFF
Identifier via the rotary encoder switches.
Example: Setting for the value 52
(3
×
16) + (4
×
1) = 52
The value set via the rotary encoder switches is used once when the mains is switched on or after a network restart with 0x2360 (P508.00) = 1. A changed value during operation will only become valid after the network has been restarted.
As an alternative, a master can also use station alias addresses of the slaves that are configured and unambiguous in the network. For this purpose, a station alias address must be saved in the EEPROM of the device by setting the corresponding register.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2361:004
(P510.04)
EtherCAT settings: Device ID
(EtherCAT sett.: Device ID)
0 ... [0] ... 65535
–
From version 02.00
 
Setting of the identifier unambiguous in the network (Explicit Device Identification).
This setting is only valid for rotary encoder switch setting 0 (0x00).