Information on the network
The following parameters show information on the network.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2382:001
(P511.01)
|
Active PROFINET settings: IP address
(PROFINET diag.: IP address)
–
Read only
–
From version 02.00
|
Display of the active IP address.
|
|
|
0x2382:002
(P511.02)
|
Active PROFINET settings: Subnet
(PROFINET diag.: Subnet)
–
Read only
–
From version 02.00
|
Display of the active subnet mask.
|
|
|
0x2382:003
(P511.03)
|
Active PROFINET settings: Gateway
(PROFINET diag.: Gateway)
–
Read only
–
From version 02.00
|
Display of the gateway address.
|
|
|
0x2382:004
(P511.04)
|
Active PROFINET settings: Station name
(PROFINET diag.: Station name)
–
Read only
–
From version 02.00
|
Display of the active station name.
|
|
|
0x2382:005
(P511.05)
|
Active PROFINET settings: MAC Address
(PROFINET diag.: MAC Address)
–
Read only
–
From version 02.00
|
Display of the active MAC address.
|
|
|
0x2388
(P516.00)
|
PROFINET status
(PROFINET status)
–
Read only
–
From version 02.00
|
Bit coded display of the current Bus status.
|
|
|
Bit 0
|
Initialized
|
The network component is initialised.
|
|
|
Bit 1
|
Online
|
After initialisation, the network component waits for a communication partner and the system power-up.
|
|
|
Bit 2
|
Connected
|
The network component has established a cyclic I/O communication relationship to a communication partner.
|
|
|
Bit 3
|
IP address error
|
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
|
|
|
Bit 4
|
Hardware fault
|
||
|
Bit 6
|
Watchdog elapsed
|
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e.g. by cable break or failure of the IO Controller.
–
PROFINET communication changes to the "No_Data_Exchange" state.
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in 0x2859:001 (P515.01) is triggered in the inverter.
|
|
|
Bit 7
|
Protocol error
|
||
|
Bit 8
|
PROFINET stack ok
|
||
|
Bit 9
|
PROFINET stack not configured
|
||
|
Bit 10
|
Ethernet controller fault
|
||
|
Bit 11
|
UDP stack fault
|
||
|
0x2389:001
(P517.01)
|
PROFINET error: Error 1
(PROFINET error: Error 1)
–
Read only
–
From version 02.00
|
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:002 (P517.02).
|
|
|
0
|
No error
|
||
|
1
|
Reserved
|
||
|
2
|
Unit ID unknown
|
||
|
3
|
Max. units exceeded
|
||
|
4
|
Invalid size
|
||
|
5
|
Unit type unknown
|
||
|
6
|
Runtime plug error
|
||
|
7
|
Invalid argument
|
||
|
8
|
Service pending
|
||
|
9
|
Stack not ready
|
||
|
10
|
Command unknown
|
||
|
11
|
Invalid address descriptor
|
||
|
0x2389:002
(P517.02)
|
PROFINET error: Error 2
(PROFINET error: Error 2)
–
Read only
–
From version 02.00
|
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:001 (P517.01).
|
|
|
Bit 7
|
IP address error
|
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
|
|
|
Bit 8
|
Station name problem
|
The station name must be assigned according to the PROFINET specification.
|
|
|
Bit 9
|
DataExch left
|
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e. g. by cable break.
–
PROFINET communication changes to the "No_Data_Exchange" state.
–
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in 0x2859:001 (P515.01) is triggered in the device.
|
|
|
Bit 10
|
Stack boot error
|
||
|
Bit 11
|
Stack online error
|
||
|
Bit 12
|
Stack state error
|
||
|
Bit 13
|
Stack revision error
|
||
|
Bit 14
|
Initialization problem
|
The stack cannot be initiated with the user specifications. A reason might be, e. g., a station name that does not correspond to the PROFINET specification.
|
|
|
Bit 15
|
Stack init error
|
||