Status LEDs

Information about the PROFIBUS status can be obtained quickly via the "NS" and "NE" LED displays on the front of the inverter.
 
The meaning can be seen from the table below.
LED "NS" (green)
LED "NE" (red)
Status/meaning
off
off
No supply voltage available, network deactivated, not initialised, or firmware download active.
on
Connected with master, control running, "Data Exchange" state active.
blinking
Not connected, control stopped, or no data exchange.
blinking
blinking
Watchdog monitoring time elapsed.
Any
Flashing
PROFIBUS parameterisation error.
Flashing 2 x
PROFIBUS configuration error.
off
on
Invalid station address set or non-correctable error.