IP settings

IP basic settings
The basic IP settings are required to let the engineering software access the network nodes (PLC, inverter) directly via Ethernet.
The PC with the engineering software must be in the same network as the devices to be configured.
First, configure the PC so that this condition is fulfilled.
The required steps are described by the example of the operating system Microsoft® Windows® 7.
How to define the IP basic settings:
1.
Call the "Network and sharing center" under "Control panel".
 
2.
Select "Change adapter settings" (observe administrator rights!).
 
3.
Select the network to be configured (double-click), e. g.:
The network nodes (PLC, inverter) must be connected to the network.
 
An internal web server is supported. It can be addressed via the IP address defined in the parameter. Protect access to the web server, e.g. with a firewall, and follow your internal IT security guidelines.
 
The status dialog box of the network is opened.
 
4.
Click "Properties".
The properties dialog box of the network is opened.
 
5.
Select "Internet protocol version 4 (TCP/IPv4)" and click "Properties".
The properties dialog box of the "Internet protocol version 4 (TCP/IPv4)" is opened.
 
6.
Enter the IP address, the subnet mask and, if required, the gateway address under "Use the following addresses".
 
7.
Click "OK".
 
The IP basic settings are now completed.
 
Set IP address
The two rotary encoder switches at the front of the device serve to set the IP address in terms of hardware.
Setting
Addressing
0x00
IP address via the parameter 0x23B1:001 (P510.01).
0x01 ... 0xFF
Setting of the 4th byte of the IP address via the rotary encoder switch.
192.168.124.[setting]
Example: Setting for the value 52
(3
×
16) + (4
×
1) = 52
The value set via the rotary encoder switches is used when the mains is switched on or after a network restart with 0x23B0 (P508.00) = 1. A changed value during operation will only become valid after the network has been restarted.
–
0x23B3 (P509.00) shows the switch setting at the last mains connection.
 
–
0x23B2:001 (P511.01) shows the active IP address.
 
 
Time-To-Live (TTL)
The TTL value (8-bit value) limits the number of routers a sent package passes on the way to its target.
–
0x23A1:006 (P510.06): Time-to-live value (TTL)
 
 
The parameters for the IP settings of the inverter are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23B1:001
(P510.01)
Modbus -TCP/IP settings: IP address
(MBTCP settings: IP address)
0.0.0.0 ... [192.168.124.16] ... 255.255.255.255
–
From version 04.00
 
Set IP address.
The default setting 276605120 corresponds to the IP address 192.168.124.16.
–
276605120 = 0x107CA8C0
à
 0xC0.0xA8.0x7C.0x10 = 192.168.124.16
 
0x23B1:002
(P510.02)
Modbus -TCP/IP settings: Subnet
(MBTCP settings: Subnet)
0.0.0.0 ... [255.255.255.0] ... 255.255.255.255
–
From version 04.00
 
Set subnet mask.
The default setting 16777215 corresponds to the subnet mask 255.255.255.0.
–
16777215 = 0xFFFFFF
à
 0xFF.0xFF.0xFF.0x00 = 255.255.255.0
 
0x23B1:003
(P510.03)
Modbus -TCP/IP settings: Gateway
(MBTCP settings: Gateway)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
–
From version 04.00
 
Set gateway address.
Example
The setting 276344004 corresponds to the gateway address 196.172.120.16.
–
276344004 = 0x1078ACC4
à
 0xC4.0xAC.0x78.0x10 = 196.172.120.16
 
0x23B1:005
(P510.05)
Modbus -TCP/IP settings: IP configuration
(MBTCP settings: IP configuration)
–
From version 04.00
 
Set IP configuration.
0
Stored IP
The currently saved IP configuration is used.
1
BOOTP
The IP configuration is assigned by the client via BOOTP.
2
DHCP
The IP configuration is assigned by the client via DHCP.
The assignment of a gateway address that is not in the same subnetwork as the IP address, is denied.
0x23B1:006
(P510.06)
Modbus -TCP/IP settings: Time-to-live value (TTL)
(MBTCP settings: TTL value)
1 ... [32] ... 255
–
From version 04.00
 
Setting of the TTL value for the validity of data packages in the network.
0x23B1:011
(P510.11)
Modbus -TCP/IP settings: Secondary port
(MBTCP settings: Secondary port)
0 ... [502] ... 65535
–
From version 04.00
 
Set port number for a second port.