Standard mapping

RPDO mapping
For the process data from the master to the inverter, the following data mapping is preset in the device description file:
1.
NetWordIN1 data word 0x4008:001 (P590.01)
 
2.
Network setpoint frequency (0.01) 0x400B:005 (P592.05)
 
3.
16 bit selectable output data, mapped to: "Keypad setpoints: Process controller setpoint" 0x2601:002 (P202.02)
 
Function assignment of the NetWordIN1 data word
Bit
Default setting
For details and configuration, see
0
Not active (reserve)
1
Not active (reserve)
2
Activate quick stop
3
Not active (reserve)
4
Run forward (CW)
5
Activate preset (bit 0)
6
Activate preset (bit 1)
7
Reset error
8
Not active (reserve)
9
Activate DC braking
10
Not active (reserve)
11
Not active (reserve)
12
Reverse rotational direction
13
Not active (reserve)
14
Not active (reserve)
15
Not active (reserve)
Specifying the frequency setpoint
–
The specification is made unsigned (independent of the direction of rotation) as integer in the resolution [0.01 Hz].
 
–
The direction of rotation is defined in the default setting via bit 12 of the NetWordIN1 data word.
 
–
Example: 4560 = 45.60 Hz
 
 
TPDO mapping
For the process data from the inverter to the master, the following data mapping is preset in the device description file:
1.
NetWordOUT1 data word 0x400A:001 (P591.01)
 
2.
Network setpoint frequency (0.01) 0x400B:005 (P592.05)
 
3.
Motor current 0x2D88 (P104.00)
 
Status assignment of the NetWordOUT1 data word
Bit
Default setting
For details and configuration, see
0
Ready for operation
1
Not connected
2
Operation enabled
3
Fault active
4
Not connected
5
Quick stop active
6
Running
7
Device warning active
8
Not connected
9
Not connected
10
Setpoint speed reached
11
Current limit reached
12
Actual speed = 0
13
Rotational direction reversed
14
Release holding brake
15
Inverter disabled (safety)
Output of the actual frequency value
–
The output is made unsigned (independent of the direction of rotation) as integer in the resolution [0.01 Hz].
 
–
An active reversal is displayed via bit 13 of the NetWordOUT1 data word.
 
–
Example: 4560 = 45.60 Hz