0x39-Safety Supervisor Object
The "Safety Supervisor Object" is supported in the "Baseline Safety Supervisor" functionality.
The safety configuration can only be transferred to the inverter in the "EASY Starter" and in the "PLC Designer" via the +Safety parameter list+.
|
Attribute ID
|
Service
|
Name
|
Data type
|
Information
|
|
11
|
Get
|
Device Status
|
USINT
|
Device status
1 Self-Testing
2: Idle
3: Self-Test Exception
4: Executing
5: Abort
6: Critical Fault
|
|
12
|
Get
|
Exception Status
|
BYTE
|
Alarm and Warning Status
–
Bit 7 is always "0".
–
Only the "Basic Method" is supported.
|
|
15
|
Get/Set
|
Alarm enable
|
BOOL
|
Activates (1) or deactivates (0) the process of setting exception bits by the Safety Supervisor Object.
|
|
16
|
Get/Set
|
Warning enable
|
BOOL
|
|
|
25
|
Get
|
Configuration UNID
|
10 Octets
|
CFUNID - Identifies the owner of a device configuration.
–
Only the tool-only configuration is supported (all octets 0xFF).
|
|
26
|
Get
|
Safety Configuration Identifier (SCID)
|
10 Octets
|
The signature of the safety configuration (SCID) is derived from the Safety Configuration CRC (SCCRC) and the Safety Configuration Time Stamp (SCTS).
|
|
27
|
Get
|
Target UNID (TUNID)
|
10 Octets
|
The current Target UNID (TUNID) of the device.
–
Can only be set via the +Safety parameter list+.
|
|
28
|
Get
|
Output Connection Point Owners
|
|
|
|
Number of Array Entries
|
UINT
|
Number of OCPUNID structure entries
–
Only "1"
|
||
|
Output Owners
|
|
|
||
|
OCPUNID
|
10 Octets
|
The OCPUNID for the output resource
|
||
|
ePath Size
|
USINT
|
Path size, number of bytes
|
|
Service code
|
Name
|
Information
|
|
0x0E
|
Get_Attribute_Single
|
Outputs the value of a specific attribute.
|
|
0x10
|
Set_Attribute_Single
|
Changes the value of a specific attribute.
|
Safe parameter setting