Diagnostics
Status LEDs
When CIP Safety communication is set, the network status LEDs "MS" and "NS" display CIP Safety status information.
DANGER!Unreliable status information possible due to LEDs.
LEDs are not reliable status displays. It is not guaranteed that the LEDs provide exact information.
Possible consequences: Death or severe injuries
▶
Only use LEDs for general diagnostics during commissioning or troubleshooting.
▶
Do not use LEDs as status displays.
The "MS" LED indicates the CIP Safety Supervisor State:
|
LED "MS" (green/red)
|
CIP Safety
Supervisor State
|
State/meaning
|
|
off
|
No Power
|
The device is not supplied with power.
|
|
on (green)
|
Executing
|
The device is ready for operation and the secure I/O connection has been established.
|
|
blinking green
|
Idle
|
No IP address or no safe I/O connection.
|
|
blinking red
|
Abort
|
The device has a rectifiable fault. There is an addressing conflict with the node ID.
|
|
on (red)
|
Critical Fault
|
The device has a fault that cannot be rectified.
|
|
blinking green/red
|
Device Self-Testing
|
The device performs a self-test.
|
The "NS" LED indicates the CIP Safety network status:
|
LED "NS" (green/red)
|
CIP Safety-network status
|
State/meaning
|
|
off
|
No IP address
|
The network option is not supplied with power or has not yet received an IP address.
|
|
on (green)
|
Connected
|
The network option is working properly and has established a connection to the originator.
|
|
blinking green
|
No connections
|
The network option
–
works perfectly,
–
has been assigned an IP address,
–
has not yet been integrated into the network by the originator.
|
|
blinking red
|
Connection Timeout
|
A timeout has occurred.
|
|
on (red)
|
Duplicate IP
|
The network option cannot access the network (IP address conflict).
|
|
blinking green/red
|
Device Self-Testing
|
The network option performs a self-test.
|
Diagnostic parameter