Preconditions
–
The CIP Safety
™
safety protocol is supported (bit 2 in 0x212C:003 is set).
 
–
The network selection is set to "EtherNet/IP". 0x231F:005
 
–
Current EDS file
 
–
The EDS file can be used to integrate Lenze EtherNet/IP devices into the EtherNet/IP configuration software of PLC manufacturers.
 
–
 
 
 
Configure safety configuration
–
Before integrating the inverter into a safety network, the safe parameter set must be reset for each device.
 
–
The "Safety Network Number" (SNN) must be unique for each safety network or safety subnet in the entire system.
 
–
The user must carefully check the effects of device combinations with different SIL levels in the safety network.
 
 
Verify safety configuration
–
The signature of the security configuration (SCID) is automatically verified via the checksums.
 
–
The user must visually check whether all safe configuration data has been correctly downloaded to the inverter.
 
–
When a safety device is configured directly from a workstation, the user must compare the transferred SCID data and configuration data with the SCID data and configuration data originally viewed in the workstation.
 
–
If the user configures safety connections with a SCID = 0, the user is responsible for ensuring that the originator (safety master) and target (inverter) are configured correctly.
Please note the following:
–
This configuration setting bypasses the standard, automated safety configuration check!
 
–
This poses a higher risk to the safety integrity of the system.
 
 
 
 
Test and validate safety configuration
–
After installation, after each change to the safety configuration and after a device replacement, the user must test the safety configuration loaded into the inverter with user tests:
 
–
To test and verify the configuration of an originator with connection data, it must first be downloaded to the inverter. This is the only way to confirm the SCID of the inverter.
 
–
Check the signature of the safety configuration (SCID). Only then can the safety configuration be considered verified.
 
–
Check and prove the operability of the safety configuration used.
 
–
Test the configurations of the safety connections after they have been applied in the originator (safety master). Only then is it ensured that the target connection functions as intended.
 
 
–
Further information: