Preconditions
–
A source for activating the function must be configured. 0x28A8
–
Only one safe input or the safety bus can be configured as a source.
–
If a safe input is configured as a source, 0x28A9:003 Function at low level must be selected carefully, since according to the closed-circuit principle, no additional danger may emanate from normal operation or special operation.
–
A source for the ES enable switch must be configured. 0x28AE
–
A stop function for special operation must be configured. 0x28A9:001
–
A motion function for special operation must be configured. 0x28A9:002
–
If the movement is to be monitored in special operation, theSLI and SMS functions can be activated for this purpose.
The plausibility check rejects ambiguous settings until they are parameterised correctly.