0x29-Control Supervisor Object
The "Control Supervisor Object" describes all management functions of the device for the motor control.
|
Attribute ID
|
Name
|
Info / parameter
|
|
3
|
Run1
|
AC drive control word 0x5030:010: Bit 0 Run forward (CW)
|
|
4
|
Run2
|
AC drive control word 0x5030:010: Bit 1 Run reverse (CCW)
|
|
5
|
NetCtrl
|
AC drive control word 0x5030:010: Bit 5 Activate network control
|
|
6
|
State
|
AC drive status word 0x5030:110: Bit 8 Status bit 0
AC drive status word 0x5030:110: Bit 9 Status bit 1
AC drive status word 0x5030:110: Bit 10 (Drive State)
AC drive status word 0x5030:110: Bit 11 Status bit 3
|
|
7
|
Running1
|
AC drive status word 0x5030:110: Bit 2 Running forward
|
|
8
|
Running2
|
AC drive status word 0x5030:110: Bit 3 Running reverse
|
|
9
|
Ready
|
AC drive status word 0x5030:110: Bit 4 Ready
|
|
10
|
Faulted
|
AC drive status word 0x5030:110: Bit 0 Fault
|
|
11
|
Warning
|
AC drive status word 0x5030:110: Bit 1 Warning
|
|
12
|
FaultRst
|
AC drive control word 0x5030:010: Bit 2 Fault reset
|
|
13
|
FaultCode
|
0x5032:53 Error code
|
|
15
|
CtrlFromNet
|
AC drive status word 0x5030:110: Bit 5 Network control active
|