Mark window and mark register

Set Activate tool mark window parameter = TRUE to activate the functionality of the mark window. 0x5041:129
Set Activate tool mark window parameter = FALSE to edit each mark. 0x5041:129
Set Mark window teaching parameter = 1 to set the mark window with the teach-in function. 0x5041:015
In the Control signals parameter, set bit 22 to activate the mark window in the Tool mark window size parameter learned via the teach-in function for the following marks.
–
Tool mark window size 0x5041:126
 
–
Control signals 0x5040:010 bit 22
 
The following table provides information on the status of the mark window:
Parameter name
Parameter index
Bit status
Status
Activate tool mark window
TRUE
Mark window active
FALSE
Mark window deactivated
Mark window teaching
1
Mark window of the tool correction is learned
0
Mark window of the master value correction is learned
 
The figure shows the use of a mark stack. The distance from the mark sensor to the tool is greater than the set mark distance.
Fig. 1: Systematic representation of the mark stack with a pocket-type conveyor
Mount the mark sensor as close as possible to the axis. The further from the axis the mark sensor is mounted, the more imprecise the cuts will be.
Up to 64 mark signals are managed in the mark stack. These marks are available to the system at the right time to delay the mark register length. This allows the tool to be corrected to the correct mark signal.
 
The distance between the touch probe sensor and the position where the tool starts is assigned via the Tool sensor distance parameter. 0x5041:121
The "mark stack" function is automatically activated when the Tool sensor distance parameter is greater than der Cycle length parameter.
Parameter
–
Tool sensor distance 0x5041:121
 
–
Cycle length 0x500A:031
 
After a mark has been detected, the value of the mark deviation is released for correction only if the position in the register cycle has covered the distance of the mark register.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:031
Cycle length
0.0001 ... [360.0000] ... 214748.3647
–
Setting can only be changed if the inverter is disabled.
 
The cycle length for an unlimited traversing range defines the position where the measuring system is repeated (position return to 0).
0x5041:014
Activate mark window
false
Disabled
true
Enabled
0x5041:015
Mark window teaching
0
Master value correction
1
Tool correction
0x5041:120
Activate tool correction
false
FALSE
true
TRUE
0x5041:121
Tool sensor distance
0.0000 ... [360.0000] ... 214748.3647
0x5041:126
Tool mark window size
0.0000 ... [40.0000] ... 214748.3647
0x5041:127
Tool mark window offset
0.0000 ... [0.0000] ... 214748.3647
0x5041:129
Activate tool mark window
false
Disabled
true
Enabled
0x5042:140
Tool sensor set position
–
Read only