Defining the winding direction

In order for the feedforward control values and the interference compensation to act in the required direction, the winding direction must be adapted to the material flow direction. The sign in the parameter Winding direction with line velocity > 0 defines whether the winder drive operates as an unwinder or a rewinder. 0x5051:011
Once this winding direction has been defined in the parameter Winding direction with line velocity > 0, the winder will automatically switch the winding direction when the sign of the line speed signal changes.
The current winding direction is displayed in bit 17 = TRUE of the parameter Status signals. 0x5050:110 Bit 17
Fig. 1: Effective direction of speed and torque as a function of the material flow
 
Minimum line velocity
The minimum line velocity is defined in the Minimum line velocity parameter. The parameter Minimum line velocity is used to set the lower limit value.
The winder permanently follows the line velocity, regardless of the height, otherwise there is a risk of material looseness or tearing of the material. Below the minimum line velocity, the diameter is maintained. In the case of the dancer position control, the I component is reset.
Fig. 2: Maintain diameter at VLine < VLine:min
 
Checking the winding direction
The winder is without material.
 
How to check the winding direction:
1.
Enable tension-controlled (open loop) operation. 0x5050:010 Bit 18 TRUE
 
2.
Set the parameter Winding direction with line velocity > 0 to TRUE. 0x5051:011
The material will now be unwound when there is a positive line speed signal.
 
3.
Set the parameter Winding direction with line velocity > 0 to FALSE. 0x5051:011
The material will now be rewound when there is a positive line speed signal.
 
 
How to configure the tensile force characteristic:
1.
Set the tensile force setpoint to 300 N. 0x5051:013
 
2.
Set the parameter Gradient of tension characteristic to 75 %. 0x5052:001
The tensile force decreases with increasing diameter from 300 N to 225 N.
The winding direction check is now complete.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x5051:009
Actual line velocity
–
Read only: x.xxxx mm/s
 
The parameter is resolved with 4 decimal positions. The parameter has the unit [mm/s].
0x5051:011
Winding direction with line velocity > 0
false
Rewinder
Rewind active
true
Unwinder
Unwind active
0x5051:012
Line velocity reference
0.0000 ... [1000.0000] ... 214748.3647 mm/s
0x5051:013
Min. line velocity
-214748.3648 ... [1.0000] ... 214748.3647 mm/s