Alarm group

An alarm group combines several alarms or other alarm groups in a logical unit.

Alarm groups are represented by the Alarm groups node in the Project Explorer. Their primary function is to group alarm definitions. Alarm groups can be nested hierarchically.

Alarm groups have the following features:

  • Alarm groups allow to organize the Alarms system module by machine units.

  • Alarm groups can be used as collective alarms. Collective alarms allow to display all alarms of an alarm group as a single alarm. Collective alarms also allow to acknowledge pending alarms of an alarm group all at once. At runtime, the origin of alarms can be determined by their alarm group.

  • The state of machine units can be logged by means of the state variable.

Parameters

The alarm group definition includes the following parameters:

Name

Description

Acknowledgment variable

Name of the variable that is used to acknowledge an alarm.

Bit number (acknowledgment variable)

Specifies the variable bit that triggers the function.

Bit number (deactivation variable)

Specifies the variable bit that triggers the function.

Bit number (state variable)

Determines the variable bit that triggers the function.

Comment

Optional comment on the definition.

Deactivation variable (Alarms)

Variable that activates and deactivates all alarms of the alarm group (at runtime).

Definition active

Determines whether the object definition is effective.

Icon

Graphic symbol to be displayed.

Name

Name of the definition.

Priority variable

Variable that saves the highest current priority.

State variable

Name of the variable that determines the state and the acknowledgment state.

Text

Sets the localizable text for the definition.

Related topics: