L_IE1P_SeverityLevel

Degrees of severity and reaction carried out

The following table shows the respective reactions depending on the connected error handler.

If only one instance of the FB L_IE1P_ErrorHandler is connected, then only one output is set at this block. The reaction can then be programmed user specifically.

For severites that do not cause a direct reaction of the connected error handler, this can be additionally controlled via the enum L_IE1P_Reaction when an error occurs.

The prioritisation of the severities depends on the value of the severity. The higher the value, the higher the priority.

Selection

Value

Acknowledge requested

Reaction
Axis_Ref

Reaction

virt. Axis_Ref

Reaction

Axes_Group

No_Response

0

None

None

None

Warning

2

Axis displays "Warning"

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

Axis displays "Warning"

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

Axes_Group displays "Warning"

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

Information

11

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_ReactionNone

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_ReactionNone

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_ReactionNone

Warning_Lock

13

X

Axis displays "Warning"

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

No reaction, only logbook entry

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

No reaction, only logbook entry

A logbook entry is generated.

An additional reaction is dependent on the associated L_IE1P_Reaction

Fault_Log

18

X

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

FAULT_QSPAPPL

19

X

Change after error stop

Stop with QSP Appl. Ramp (Sub/48+49), drive remains enabled

Change after error stop

Stop with QSP Appl. Ramp (Sub/48+49), drive remains enabled

Change of the axes group after error stop

Stop with QSP Appl. Ramp (Sub/48+49), drive remains enabled.

Fault_QspAppl

20

X

Change after error stop

Stop with QSP Drive Ramp (0x6085/0), drive remains enabled.

see FAULT_QSPAPPL

Change of the axes group after error stop

Stop with QSP Drive Ramp (0x6085/0), drive remains enabled.

Fault_Qsp_Cinh

21

X

Change of the axes group after error stop

Stop with QSP Drive Ramp (0x6085/0), after reaching standstill, the drive is inhibited

FAULT_QSPAPPL, then Axis_Enabled changes to False

Change of the axes group after error stop

Stop with QSP Drive Ramp (0x6085/0), after reaching standstill, the drive is inhibited

Fault_Cinh

23

x

Change after error stop

Disable drive controller immediately

Wechsel nach Errorstop.

Axis_Enabled changes to False

Change of the axes group to error stop.

All axes inhibited

Fault

30

x

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

By default no reaction, only log book entry

The reaction is dependent on the associated L_IE1P_Reaction

Special cases

If the error reaction is triggered when the axis is inhibited, the axis changes to the error state but no reaction is executed