"Pre-Operational" EtherCAT state is not achieved

During the start-up of the EtherCAT bus, a check is carried out at the transition from Init to Pre-Operational to determine whether the physical bus configuration corresponds to the configured bus configuration. If theses configurations are different, the master does not enter the Pre-Operational state. Furthermore, the slaves are initialized during the transition from Init to Pre-Operational. If this fails because, for instance, a slave rejects the configuration, the master does not enter the Pre-Operational state.