Error during process data transfer
A faulty EtherCAT I/O mapping causes errors during the process data transfer.
|
Cause
|
Use of logic addresses
–
In the »PLC Designer« application, access does not take place symbolically but directly via the I/O addresses (%Ixx, %Qxx) of the EtherCAT input and output objects and the bus structure, the PDO selection etc. have changed.
|
|
Error message
|
-
|
|
Remedies
|
In the »PLC Designer« application, the input and output objects must be accessed via individual non-ambiguous variables. The variable names must comply with the IEC 61131 syntax (no space characters and leading digits in the variable names).
|
|
Cause
|
Manual definition of the logic address in the EtherCAT I/O mapping
|
|
Error message
|
-
|
|
Remedies
|
It is not permissible to manually manipulate the I/O addresses for the EtherCAT bus!
|