The EtherCAT master reports "SYNC error - BusCycleTask is not in-sync"
|
Cause
|
The EtherCAT master BusCycleTask is synchronized with the DC reference clock so that the PLC task and the EtherCAT bus run synchronously. If the EtherCAT master BusCycleTask does not have the highest priority, it can be displaced by other tasks and thus loses its synchronicity.
|
|
Error message
|
EtherCAT_Master: SYNC error - BusCycleTask is not in-sync
|
|
Remedies
|
Check the following settings and correct them if necessary. The bus cycle task of the EtherCAT master must have the highest priority task!
–
Task configuration: Task priority
–
Device/PLC settings: BusCycle options
–
EtherCAT_Master/EtherCAT IO mapping: BusCycle options
|