A sent frame is not returned to the master

Cause
A frame sent by the master does not return to the master until the next cycle.
–
The task utilization is too high, such that a sent frame takes longer than the time to the next start of the bus cycle task.
 
–
The EtherCAT bus cycle task does not have the highest IEC task priority or another task has the same IEC task priority, such that the EtherCAT bus cycle task is suppressed.
 
–
Due to an error, the slave does not forward any frames.
 
–
Only a switch or an ET2000 is connected to the controller, but no further slave.
 
Error message
–
EtherCAT_Master: Frame response error (repeated 1 time)
 
–
EtherCAT_Master: Frame response error (repeated 10 times)
 
–
EtherCAT_Master: Frame response error (repeated 100 times)
 
Remedies
–
Reduce the program code or increase the bus task cycle time.
 
–
Correct the bus structure.
 
–
Correct the slave error.
 
–
Assign the sole and highest IEC task priority to the EtherCAT bus cycle task.