The I/O configuration is invalid
When the status changes from Pre-Operational to Safe-Operational, a slave reports Invalid Output Configuration.
|
Cause
|
The process data configuration of a slave is not correct.
–
In case of a modular device such as the I/O system 1000 (EPM-Sxxx), the configuration in the project does not comply with the real assembly.
–
More process data than permissible is mapped for the device.
|
|
Error message
|
–
[DeviceName] (1001): Slave signals Error. AL state: ‘PRE-OPERATIONAL' (0x12), AL state code: 'Invalid Input Configuration' (0x1E)
–
[DeviceName] (1001): Slave signals Error. AL state: ‘PRE-OPERATIONAL' (0x12), AL state code: 'Invalid Output Configuration' (0x1D)
|
|
Remedies
|
–
In case of modular devices such as the I/O system 1000 (EPM-Sxxx): Correct the control configuration in the »PLC Designer« (adjustment with the real structure).
–
Reduction of the process data: The maximum process data length must not be exceeded (see also the device documentation).
|