The drive shafts do not rotate

Cause
The EtherCAT bus could not be set to the Operational state
Error message
-
Remedies
 
Cause
Clicking noise of the shafts after out-of-sync
Error message
-
Remedies
 
Cause
Clicking noise of the shafts after out-of-sync
If due to a fault, the preset DC deviation limit is exceeded, a re-synchronization of the DC slaves is carried out until the slaves are synchronized again (In-Sync) and the DC deviation is under the preset limit value again.
Currently, the Lenze controller is not re-synchronized to the distributed clocks, such that the sync pulses of the master and the ones of the slaves are different.
Error message
EtherCAT_Master: DC slaves 'out-of-sync'. Deviation xxxxxxxx ns
Remedies
Restart the EtherCAT fieldbus so that the DC slaves and the DC master synchronize again.
 
Cause
Faulty SoftMotion scaling/mapping
With SoftMotion scaling/mapping, the increments per revolution are not set.
Error message
-
Remedies
Check the following settings and correct them if required:
–
Gearbox ratio in the »PLC Designer« application
 
–
Mapping settings in the master configuration
 
When the Lenze controller is started, the complete configuration/PDO mapping is written into the EtherCAT slaves. Mapping entries, e.g. from the »Engineer«, will then be overwritten.