The output shafts make a cracking sound
For motion applications in drive technology, a defective synchronization of 2 shafts leads to an audible clicking noise.
|
Cause
|
The task and DC cycle times set in the logic/motion system differ.
|
|
Error message
|
-
|
|
Remedies
|
Adjust the task cycle time and DC cycle time.
|
|
Cause
|
Wiring error: The EtherCAT terminals (IN/OUT) of the slave were inverted. A fieldbus scan does not indicate this error!
|
|
Error message
|
EtherCAT_Master: Set master 'Operational' failed. DCM not in-sync
|
|
Remedies
|
Correct wiring. Afterwards, reload the »PLC Designer« application into the automation system.
|
|
Cause
|
Clicking noise of the shafts after "out-of-sync"
If due to a fault, the preset DC deviation limit is exceeded, a re-synchronization of the DC slaves is carried out until the slaves are synchronized again ("In-Sync") and the DC deviation is under the preset limit value again.
Currently, the Lenze controller is not re-synchronized to the distributed clocks, such that the sync pulses of the master and the ones of the slaves are different.
|
|
Error message
|
EtherCAT_Master: DC slaves 'out-of-sync'. Deviation xxxxxxxx ns
|
|
Remedies
|
Restart the EtherCAT fieldbus so that the DC slaves and the DC master synchronize again.
|
|
Cause
|
Wrong selection of the device sync source. After the sync source has been changed, the subsequent download and the setting of the slave to the Operational state may fail.
|
|
Error message
|
-
|
|
Remedies
|
–
Manual setting of the code
–
Repeated download with PLC start
–
Restart the EtherCAT fieldbus by resetting the SoftMotion drive
|