Commissioning

In the following, the steps required for controlling the inverter via POWERLINK are described.
 
Parameterisation required
1.
Activate network control: 0x2631:037 (P400.37) = "TRUE [1]"
 
2.
Set network as standard setpoint source: 0x2860:001 (P201.01) = "Network [5]"
 
3.
Set the node address.
 
–
Each network node must be provided with a unique node address (node ID).
 
–
 
 
4.
Save parameter settings: 0x2022:003 (P700.03) = "On / start [1]".
 
5.
Switch the inverter off and then on again in order that the changed communication settings can get effective.
 
6.
Check the readiness for operation of the inverter by means of the LED status displays.
 
–
The red LEDs must be off, otherwise an error has occurred.
 
–
The green LED at the RJ45 socket is on if a physical POWERLINK connection is available.
 
–
Details: Status LEDs 
 
 
In the default setting, the digital input DI1 is assigned the "Run" function. If the network control is activated, this function serves as "start enable" for start commands via network. Hence, the digital input DI1 must be set to the HIGH level in order that the motor can be started via the network.
 
 
Start network
The network is automatically started if you first set all controlled nodes (as described above) and then the managing node.
Otherwise, there are the following two options:
a.
Switch all network nodes off and then on again or
 
b.
make a fault reset at the managing node (node ID 240).
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23C0
POWERLINK communication
–
From version 05.00
 
Restart / stop communication.
–
When the device command has been executed successfully, the value 0 is shown.
 
0
No action/no error
Only status feedback
1
Restart with current values
Restart communication with the current values.
2
Restart with default values
Restart communication with the standard values.
10
In progress
Only status feedback
11
Action cancelled
12
Fault