Process data transfer
POWERLINK transfers process data, parameter data, configuration data and
diagnostic data between the managing node and the involved controlled nodes in the network.
Depending on their time-critical behaviour, the data is transmitted via
corresponding communication channels.
Details
–
Process data is transmitted cyclically between the managing node and the controlled node (permanent exchange of current input and output data).
–
The transfer of process data is time-critical.
–
The process data serves to control the POWERLINK nodes.
–
The process data can be directly accessed by the managing node. The data in the PLC, for instance, are directly stored in the I/O area.
–
The contents of the process data are defined via I/O data mapping.
–
Process data is not saved in the device.
Default mapping
Process data (RxPDO):
–
0x4008:001 (P590.01) (NetWordIN1)
–
0x400B:013 (P592.13) (Network frequency setpoint [+/-16384])
Process data (TxPDO):
–
0x400A:001 (P591.01) (NetWordOUT1)
–
0x400C:009 (P593.09) (Frequency [+/-16384])
–
0x2D88 (P104.00) (Motor current)
–
0x4050:002 (internal parameters)
Dynamic mapping is supported (displayed by bit 6 of the NMT_FeatureFlags_U32 0x1F82).
Dynamic mapping
Dynamic mapping is processed in the “Automation Suite" (engineering software) by displaying a list of possible parameters "Sent" and “Received". From this list, a dedicated configuration must be selected and saved on the master system. When the system is started, the desired mapping is written from the master into the slave (inverter).