Basic setting and options

Each network node must be provided with a unique node address (node ID).
 
Setting the node address
The node address can be set in 0x23C1:004 or via the two rotary encoder switches on the front of the inverter.
–
If both rotary encoder switches are set to "0", the value set in 0x23C1:004 is used as node address.
 
–
The setting that is active when the inverter is switched on is the effective setting.
 
–
A value changed during operation only gets valid when the device is restarted.
 
–
Valid node addresses for controlled nodes: 1 ... 239
 
–
The resulting IP address is "192.168.100.[node address]".
 
Example: Setting of the node address 52 via the rotary encoder switches
–
52 = 3 x 16 + 4 x 1
 
–
The resulting IP address is "192.168.100.52".
 
Note: If the value set via the rotary encoder switches is higher than 239, the node address is set to 239.
Diagnostic parameters:
–
0x23C2:004 displays the active node address.
 
–
0x23C3 displays the switch setting at the last mains switching.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x1006
NMT_CycleLen_U32
0 ... [0] ... 4294967295
–
From version 05.00
 
Length of the POWERLINK cycle in μs.
–
The selected value must correspond to the real bus cycle time in order that the internal monitoring modes operate correctly.
 
–
In the configured state, all POWERLINK nodes must be set to an identical value.
 
0x1F98:007
NMT_CycleTiming_REC: MultipleCycleCnt_U8
0 ... [0] ... 255
–
From version 05.00
 
Setting of the maximum number of multiplexed cycles.
–
In case of the setting "3", the multiplexed cycle is repeated every 3 cycles.
 
–
Within one multiplexed cycle, the nodes are queried according to the values in 0x1F9B:xxx. If, for instance, the value "2" is entered for a node in 0x1F9B:xxx, it is always only queried in the 2nd of 3 multiplexed cycles.
 
0x1F98:009
NMT_CycleTiming_REC: Prescaler_U16
0 ... [2] ... 1000
–
From version 05.00
 
Configuration of the switching rate of the SoC-PS flag.
0x1F99
NMT_CNBasicEthernetTimeout_u32
0 ... [0] ... 4294967295
–
From version 05.00
 
Setting of the maximum time the booting controlled node waits for the managing node.
–
If the controlled node detects a managing node within the time, the controlled node changes to the "NMT_CS_PREOPERATIONAL_1" state. Otherwise, the controlled node changes to the "Basic Ethernet Mode" state.
 
0x1F9A
NMT_HostName_VSTR
–
From version 05.00
 
Setting of a DNS-compatible device name.
–
The length is limited to 20 characters.
 
–
The device name must be clear within the network domain.
 
–
The device name starts with a letter ends with a letter or a number.
 
Permitted characters:
–
Letter (A ... Z, a ... z)
 
–
Numbers (0 ... 9)
 
–
Hyphen (-)
 
0x1F9E
NMT_ResetCmd_U8
–
Read only
 
–
From version 05.00
 
This object enables the managing node to execute a reset command in the controlled node.
 
Note!
A reset command at a single POWERLINK node in the network can cause cycle and monitoring errors.
0x23C1:004
POWERLINK settings: Node ID
0 ... [0] ... 239
–
From version 05.00
 
Setting of the unique node address (node ID) in the network.
–
The node address set here is only effective if both rotary encoder switches are set to "0".
 
–
In the default setting "0", the rotary encoder switch setting is used.
 
–
The resulting IP address is "192.168.100.[node address]".
 
–
A changed node address only becomes effective after a restart of the device.