Information on the network
The following parameters show information on the network.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2362:004
(P511.04)
|
Active EtherCAT settings: Device ID
(EtherCAT diag.: Device ID)
–
Read only
–
From version 02.00
|
Display of the clear device address in the network which is defined via rotary encoder switch or object 0x2361:004 (P510.04).
|
|
|
0x2362:006
(P511.06)
|
Active EtherCAT settings: Station address
(EtherCAT diag.: Station address)
–
Read only
–
From version 02.00
|
Display of the active station address.
|
|
|
0x2362:007
(P511.07)
|
Active EtherCAT settings: Tx length
(EtherCAT diag.: Tx length)
–
Read only
–
From version 02.00
|
Display of the length of the transmitted cyclic data in bytes.
|
|
|
0x2362:008
(P511.08)
|
Active EtherCAT settings: Rx length
(EtherCAT diag.: Rx length)
–
Read only
–
From version 02.00
|
Display of the length of the received cyclic data in bytes.
|
|
|
0x2363
(P509.00)
|
EtherCAT switch position
(EtherC. switch)
–
Read only
–
From version 02.00
|
Display of the current rotary encoder switch settings.
|
|
|
0x2368
(P516.00)
|
EtherCAT status
(EtherCAT status)
–
Read only
–
From version 02.00
|
Display of the current network status.
|
|
|
1
|
Initialization
|
Network initialization is active.
–
No PDO/SDO transmission.
–
Device identification is possible by network scan.
|
|
|
2
|
Pre-Operational
|
The network is active.
–
SDO transmission (CoE communication via mailbox) is possible.
–
No PDO transmission.
|
|
|
3
|
Bootstrap
|
Firmware update active.
–
For the firmware update, the FoE protocol is used.
–
No PDO transmission.
|
|
|
4
|
Safe-Operational
|
–
SDO transmission (CoE communication via mailbox) is possible.
–
PDO transmission:
– The input data in the process image are updated. – The output data from the process image are not transmitted. |
|
|
8
|
Operational
|
Normal operation
–
PDO/SDO transmission is possible.
–
Network synchronisation is successful (if used).
|
|
|
0x2369
(P517.00)
|
EtherCAT error
(EtherCAT error)
–
Read only
–
From version 02.00
|
Bit coded display of EtherCAT errors.
|
|
|
Bit 0
|
Watchdog elapsed
|
||
|
Bit 2
|
Invalid configuration
|
||
|
Bit 3
|
Stack init error
|
||
|
Bit 4
|
Invalid process data
|
||