Baud rate setting

All network nodes must be set to the same baud rate.
 
–
If the DIP switch labelled with "b" is in the OFF position at switch-on, the automatic baud rate detection function is active. If it is in the ON position, the setting in 0x2321:002 (P510.02)applies instead.
 
–
If the automatic baud rate detection function is activated, the first 5 ... 10 messages are lost after switch-on.
 
–
The active baud rate is displayed in 0x2322:002 (P511.02).
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2321:002
(P510.02)
Modbus settings: Baud rate
(Modbus sett.: Baud rate)
Optionally setting of the baud rate (instead of setting via DIP switch b).
–
The baud rate set here is only effective if DIP switch b was set to ON before mains switching. Otherwise automatic baud rate detection is active.
 
–
A change in the baud rate only becomes effective after a restart of Modbus communication.
 
–
If the automatic baud rate detection function is activated, the first 5 ... 10 messages are lost after switch-on.
 
0
Automatic
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
57600 bps
7
115200 bps