Data format setting

All network nodes must be set to the same data format.
 
–
If the DIP switch labelled with "a" is in the OFF position at switch-on, the automatic data format detection function is active. If it is in the ON position, the setting in 0x2321:003 (P510.03)applies instead.
 
–
If the automatic data format detection function is activated, the first 5 ... 10 messages are lost after switch-on.
 
–
The active data format is displayed in 0x2322:003 (P511.03).
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2321:003
(P510.03)
Modbus settings: Data format
(Modbus sett.: Data format)
Definition of the parity and stop bits.
0
Automatic
Automatic data format detection.
–
With this setting, the first 5 ... 10 messages are lost after switch-on.
 
1
8, E, 1
8 data bits, even parity, 1 stop bit
2
8, O, 1
8 data bits, odd parity, 1 stop bit
3
8, N, 2
8 data bits, no parity bit, 2 stop bits
4
8, N, 1
8 data bits, no parity bit, 1 stop bit