Example: Activation via command (only when disabled)

Activation method 0x4046 = "Via command (disable required) [0]":
–
The parameter set is selected via switches S3 and S4 (see following table).
 
–
Switch S2 activates the changeover. Since the changeover is activated with a rising edge, a button (normally-open contact) can be used instead of a switch.
 
–
Changeover is only possible if the motor is not started (switch S1 open).
 
Connection diagram
Function
Switch S1
Run
Switch S2
Load parameter set
Switch S3 ... S4
Parameter set selection:
S3
S4
Off
Off
Parameter set 1
On
Off
Parameter set 2
Off
On
Parameter set 3
On
On
Parameter set 4
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DI1 [1]
Plug X3.2 configuration
DI4 + DI3 [1]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Load parameter set
Digital input 2 [12]
Select parameter set (bit 0)
Digital input 3 [13]
Select parameter set (bit 1)
Digital input 4 [14]
Activation of parameter set
Via command (disable required) [0]
The status signals can be assigned to digital outputs. Configure digital outputs
①
The changeover is activated with the "Load parameter set" function (FALSE/TRUE edge).
②
If the inverter is enabled and the motor is started, a change-over is not possible.