Example: Activation if the selection is changed (immediately)

Activation method 0x4046 = "If the selection is changed (immediately) [3]":
–
The parameter set is selected via switches S3 and S4 (see following table). At the same time, a change of state of the selection inputs activates the changeover.
 
–
Changeover takes place immediately, even if the motor is started (switch S1 closed).
 
–
Switch S2 ("Load parameter set") is ignored in this configuration.
 
Connection diagram
Function
Switch S1
Run
Switch S2
Load parameter set (is ignored in this configuration)
Switch S3 ... S4
Parameter set selection and activation at the same time:
S3
S4
Off
Off
Parameter set 1
On
Off
Parameter set 2
Off
On
Parameter set 3
On
On
Parameter set 4
Parameter
Name
Setting for this example
Plug X3.1 configuration
DI2 + DI1 [1]
Plug X3.2 configuration
DI4 + DI3 [1]
Enable inverter
Constant TRUE [1]
Run
Digital input 1 [11]
Reset fault
Not connected [0]
Load parameter set
Digital input 2 [12]
Select parameter set (bit 0)
Digital input 3 [13]
Select parameter set (bit 1)
Digital input 4 [14]
Activation of parameter set
If the selection is changed (immediately) [3]
The status signals can be assigned to digital outputs. Configure digital outputs
①
The "Load parameter set" function is ignored in this configuration.
②
Changeover takes place by a status change of the selection inputs.
③
Changeover is also possible when the inverter is enabled and the motor has started.