Simulation of the virtual master

The technology interface is operated manually via the following parameters:
–
Simulation of control signals virtual master 0x5045:001
 
–
Simulation of status signals 0x5045:101
 
 
The Simulation of control signals for virtual master Bit 0 parameter activates the manual operation of the technology functionality. All control words are set to manual operation. 0x5045:001 Bit 0
The setpoint velocity can be switched via the Simulation of control signals for virtual master bit 1 parameter to system bus operation/fieldbus operation. 0x5045:001
The Simulation of status signals Bit 0 parameter activates the simulation of the interface. All status words are switched to manual operation. 0x5045:101 Bit 0
Fig. 1: Basic signal flow
 
Parameter
Address
Name / setting range / [default setting]
Information
0x5045:001
Simulation of control signals virtual master
0x00 ... [0x00] ... 0xFF
Bit  0
Enable control signal simulation
TRUE: Simulation of control word is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  1
Activate simulation of control word 1
TRUE: Simulation of control word 1 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  2
Activate simulation of control word 2
TRUE: Simulation of control word 2 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  3
Activate simulation of control word 3
TRUE: Simulation of control word 3 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  4
Activate simulation of control word 4
TRUE: Simulation of control word 4 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  5
Activate simulation of control word 5
TRUE: Simulation of control word 5 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  6
Activate simulation of control word 6
TRUE: Simulation of control word 6 is activated.
FALSE: The control word is transmitted via the active network interface.
Bit  7
Activate simulation of control word 7
TRUE: Simulation of control word 7 is activated.
FALSE: The control word is transmitted via the active network interface.
0x5045:101
Simulation of status signals virtual master
0x00 ... [0x00] ... 0xFF
Bit  0
Enable status signal simulation
TRUE: The simulation of the status signals is activated.
FALSE: The status signals are transmitted via the active network interface.