Speed via analog input 1
The speed source takes the form of a percentage value from analog input 1. The Diagnostics of analog input 1: Scaled percent value parameter refers to the Reference velocity for analog input 1 parameter.
–
Diagnostics of analog input 1: Scaled percent value
0x2DA4:005
0x2DA4:005–
Reference velocity for analog input 1
0x5020:009
0x5020:009The Reference velocity for analog input 1 parameter is configured and scaled in the basic settings.
The resulting setpoint velocity Virtual Master: Set velocity is used for the continuous operation or cyclic operation of the virtual master.
0x5047:001
0x5047:001Fig. 1: Front view of the plug connector X3 with analog input 1
Fig. 2: Analog input 1 as speed source
Relevant parameters of other functions
|
Address
|
Name
|
Default setting
|
Setting range
|
|
Diagnostics of analog input 1: Scaled percent value
|
x.xx % (Read only)
|
||
|
Reference velocity for analog input 1
|
500.0000
|
0.0000 ... 214748.3647
|
|
|
Virtual Master: Set velocity
|
- (Read only)
|
||