External master values
The Virtual master control signals parameter can be used to switch over the master value source when the controller is enabled.
0x5045:010 Bit 31
0x5045:010 Bit 31If bit 31 of the Virtual master control signals parameter is set to TRUE, the external master value sources are deselected. The virtual master takes over the motion control and synchronises itself via the selected master value source.
Profile calculation parameters:
–
Virtual master acceleration
0x5046:003
0x5046:003–
Virtual master deceleration
0x5046:004
0x5046:004–
Virtual master jerk
0x5046:005
0x5046:005–
Clutch-in direction virtual master 0x5046:030
If bit 31 of the Virtual master control signals parameter is set to FALSE, the master value synchronises itself with the master value source selected in the Master value source parameter.
The compensation velocity is specified via the Virtual master clutch velocity parameter.
0x5046:020
0x5046:020The synchronisation processes can be executed for the following starting conditions and target conditions:
–
From standstill to motion
–
From motion to standstill
–
From motion to motion
–
From standstill to standstill
The synchronisation processes are independent of the motion of the external master value source. Synchronisation also occurs when the real master is at a standstill.
Fig. 1: Clutch is switched from master value source to the virtual master
Fig. 2: Control bits and status bits
Relevant parameters of other functions
|
Address
|
Name
|
Default setting
|
Setting range
|
|
Virtual master acceleration
|
100000.00
|
0.00 ... 21474836.47
|
|
|
Virtual master deceleration
|
100000.00
|
0.00 ... 21474836.47
|
|
|
Virtual master jerk
|
1000000.00
|
0.00 ... 21474836.47
|
|
|
Virtual master clutch velocity
|
100.0000
|
0.0000 ... 214748.3647
|
|
|
Virtual Master: Set velocity
|
- (Read only)
|
||