Control settings

General variables such as starting values, reference variables, and signal sources must be defined before the control system of the technology application is configured.
 
The digits 1 ... 5 designate the recommended sequence during commissioning.
Fig. 1: Sequence of commissioning steps
 
Settings in
"
EASY Starter
"
:
–
Settings tab
 
–
Technology application parameter dialogue for
 
–
Application selection 0x4000
 
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
Interface selection
Fieldbus network [0]
Selection list
Application quick stop source
FALSE [0]
Selection list
Source of fault reset
FALSE [0]
Selection list
Line velocity source
External [0]
Selection list
Source of digital output 1
Ready to switch on [0]
Selection list
Display value 1
Actual tension [9]
Selection list
Display value 2
Master speed limit [8]
Selection list
Evaluation line velocity - numerator
1.0000000000
-2147483648.0000000000 ... 2147483647.0000000000
Evaluation line velocity - denominator
1.0000000000
-2147483648.0000000000 ... 2147483647.0000000000
Winding direction with line velocity > 0
0
Line velocity reference
1000.0000 mm/s
0.0000 ... 214748.3647 mm/s
Tensile force reference value
2.00 N
0.00 ... 21474836.47 N
Min. reel diameter
50.0000 mm
1.0000 ... 10000.0000 mm
Max. reel diameter
180.0000 mm
1.0000 ... 10000.0000 mm