Tension control closed loop and open loop

The technology application can be used to implement 2 winder control modes:
–
Open-loop tension control, torque-based
 
–
Closed-loop tension control, torque-based
 
The parameter Control mode for tensile force can be used to define which winder control mode is utilised. 0x5050:003
 
If no actual tensile force is available for a closed tensile force control loop, a simple tension control is used. The parameter Control method for tensile force activates simple tension control. 0x5050:003
The speed is determined by the fact that the winder follows the line velocity and must hold the web tension.
The fieldbus interface is preset as the source for the setpoint tensile force. Alternatively, the source can be set via the Source set tensile force parameter. 0x5052:005
The parameter Setpoint tensile force indicates the tensile force in [N]. 0x5052:007
In the parameter Control deviation with reduced gain, the unit [N] is used to specify up to which system deviation the reduced gain from the parameter Gain factor with reduced sensitivity tension control applies.
–
System deviation with reduced gain 0x5052:015
 
–
Gain factor with reduced sensitivity of the tension control 0x5052:016
 
Fig. 1: Signal selection
 
Reduced controller dynamics at low system deviations have a positive effect on the damping behaviour of the control loop.
 
The tolerance zone is defined by specifying a permissible system deviation in the parameter Tension controller reduced gain. 0x5052:016
The system deviation corresponds to the setpoint minus the actual value.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2DA4:005
Diagnostics of analog input 1: Scaled percent value
–
Read only: x.xx %
 
Display of the actual value at the analog input, scaled with the following parameters:
–
Minimum value for scaling. 0x2636:013
 
–
Maximum value for scaling. 0x2636:014
 
0x5020:015
Tensile force reference analog input 1
0.00 ... [2.00] ... 21474836.47 N
0x5020:020
Line velocity source
0
External
1
Load encoder
3
Synchronized with master value
0x5020:021
Actual tension source
0
External
2
Analog input 1
0x5050:013
Set tension
-21474836.48 ... [0.00] ... 21474836.47 N
Setpoint tensile force
0x5050:014
Tension control influence
0.00 ... [0.00] ... 21474836.47 %
Determine the influence of the tension control.
0x5050:015
Actual tension
-21474836.48 ... [0.00] ... 21474836.47 N
Actual tensile force
0x5051:007
Evaluation line velocity - numerator
-2147483648.0000000000 ... [1.0000000000] ... 2147483647.0000000000
0x5051:008
Evaluation line velocity - denominator
-2147483648.0000000000 ... [1.0000000000] ... 2147483647.0000000000
0x5051:036
Winder set torque
–
Read only: x.xxxx Nm
 
0x5051:096
Actual diameter
–
Read only: x.xxxx mm
 
The parameter is resolved with 4 decimal positions. The parameter has the unit [mm].
0x5052:003
External set tension
–
Read only: x.xx N
 
0x5052:004
Tensile force characteristic - actual output value
–
Read only: x.xx N
 
0x5052:005
Set tension source
0
External
1
Parameter
0x5052:006
Source of tension control influence
0
External
1
Parameter
0x5052:007
Set tension
0.00 ... [4.00] ... 21474836.47 N
0x5052:008
Tension control internal influence
0.00 ... [0.00] ... 21474836.47 %
0x5052:009
Tension control actual influence
–
Read only: x.xx %
 
0x5052:010
Set tensile force ramp
0.0000000000 ... [50.0000000000] ... 2147483647.0000000000 N/s
0x5052:011
Tension control - gain
0.00 ... [0.00] ... 21474836.47
0x5052:012
Tension control reset time
0.000 ... [0.000] ... 2147483.647 s
0x5052:013
Tension control - upper limit
0.00 ... [21474836.47] ... 21474836.47 N
0x5052:014
Tension control - lower limit
-21474836.48 ... [-21474836.47] ... 0.00 N
0x5052:015
Max. control deviation with reduced gain
0.00 ... [0.00] ... 21474836.47 N
0x5052:016
Tension controller reduced gain
0.00 ... [0.00] ... 21474836.47
0x5052:017
Tension control - set tensile force
–
Read only: x.xx N
 
0x5052:018
Adaption factor of actual tensile force
1.00 ... [100.00] ... 100.00 %
0x5052:019
Actual tensile force offset
0.00 ... [0.00] ... 21474836.47 N
0x5052:020
Filter time actual tensile force
0.000 ... [0.005] ... 10.000 s
0x5052:021
Filtered actual tensile force
–
Read only: x.xx N
 
0x5052:022
Tension control - actual output
–
Read only: x.xx N
 
0x5052:023
Max. tension at dmax and rated motor torque
–
Read only: x.xx N
 
0x5052:024
Tension control - set torque
–
Read only: x.xxxx Nm