Tension control closed loop and open loop
The technology application can be used to implement 2 winder control modes:
–
Open-loop tension control, torque-based
–
Closed-loop tension control, torque-based
The parameter Control mode for tensile force can be used to define which winder control mode is utilised. 0x5050:003
If no actual tensile force is available for a closed tensile force control loop, a simple tension control is used. The parameter Control method for tensile force activates simple tension control. 0x5050:003
The speed is determined by the fact that the winder follows the line velocity and must hold the web tension.
The fieldbus interface is preset as the source for the setpoint tensile force. Alternatively, the source can be set via the Source set tensile force parameter.
0x5052:005
0x5052:005 The parameter Setpoint tensile force indicates the tensile force in [N].
0x5052:007
0x5052:007In the parameter Control deviation with reduced gain, the unit [N] is used to specify up to which system deviation the reduced gain from the parameter Gain factor with reduced sensitivity tension control applies.
–
System deviation with reduced gain
0x5052:015
0x5052:015–
Gain factor with reduced sensitivity of the tension control
0x5052:016
0x5052:016Fig. 1: Signal selection
Reduced controller dynamics at low system deviations have a positive effect on the damping behaviour of the control loop.
The tolerance zone is defined by specifying a permissible system deviation in the parameter Tension controller reduced gain.
0x5052:016
0x5052:016The system deviation corresponds to the setpoint minus the actual value.