Torque-based tension control closed loop

The control concept of the simple open-loop tension control can be supplemented with a closed control loop.
 
The control concept is utilised when, despite friction and acceleration compensation, overly high tensile force deviations are either to be expected or have been identified.
 
In this case, the tensile force controller with PID structure has a corrective function and acts on the torque feedforward control path from the open-loop tension control. The control mode to be utilised is selected in the parameter Control mode for tensile force. 0x5050:003
Fig. 1: Basic signal flow
 
The tension control is active as soon as an influence > 0 % and a P gain Current influence of tension control are defined. 0x5052:009

In DEFAULT, the influence for the tensile force controller comes from the fieldbus interface. Alternatively, the default can be specified via the parameter Internal influence tension control. 0x5052:008
If control is to be temporarily suspended, the process controller can reset the control bit 19 = TRUE and deactivate it.
The source is switched in the Source of tension control influence parameter. 0x5052:006
Fig. 2: Source of tension control influence
 
When bit 19 of the status word is set to TRUE, the tension control setpoint is equated to the actual tension control. 0x5050:10
The effective correcting variable is set to 0 and maintained.

In the case of an actual tensile force signal with a limited resolution, a PT1 filter can have a positive effect on the control loop’s stability. When high dynamic performance is required, avoid dead time in the control loop. The filter time can be optimised in the parameter Filter time actual tensile force. 0x5052:020
The actual tensile force signal can be adapted in the parameters Adaption factor of actual tensile force and Actual tensile force offset with a gain and an offset.
Adaptation parameters
–
Adaption factor of actual tensile force 0x5052:018
 
–
Actual tensile force offset 0x5052:019
 
When the analog input constitutes the source for the actual tensile force, the reference value must be defined in the parameter Tensile force reference analog input 1. 0x5020:015
Fig. 3: Options for signal adaptation and source selection
 
The correcting variable of the PI controller is fed via a limiter. It can also be limited via the parameters:
–
Tension control - upper limit 0x5052:013
 
–
Tension control - lower limit 0x5052:014
 
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
Diagnostics of analog input 1: Scaled percent value
x.xx % (Read only)
Tensile force reference analog input 1
2.00 N
0.00 ... 21474836.47 N
Actual tension source
Analog input 1 [2]
Selection list
Tension control influence
0.00 %
0.00 ... 21474836.47 %
Actual tension
0.00 N
-21474836.48 ... 21474836.47 N
Source of tension control influence
External [0]
Selection list
Tension control internal influence
0.00 %
0.00 ... 21474836.47 %
Tension control actual influence
x.xx % (Read only)
Tension control - gain
0.00
0.00 ... 21474836.47
Tension control reset time
0.000 s
0.000 ... 2147483.647 s
Tension control - upper limit
21474836.47 N
0.00 ... 21474836.47 N
Tension control - lower limit
-21474836.47 N
-21474836.48 ... 0.00 N
Tension control - set tensile force
x.xx N (Read only)
Adaption factor of actual tensile force
100.00 %
1.00 ... 100.00 %
Actual tensile force offset
0.00 N
0.00 ... 21474836.47 N
Filter time actual tensile force
0.005 s
0.000 ... 10.000 s
Filtered actual tensile force
x.xx N (Read only)
Tension control - actual output
x.xx N (Read only)