Torque-based tension control open loop
In order to prevent sudden jumps, the tensile force setpoint is fed via a ramp generator. The ramp function is adapted to the time response via the parameter Set tensile force ramp in the application.
0x5052:010
0x5052:010The ramp must be adapted such that overly rapid setpoint value changes will not lead to instability, while still being sufficiently dynamic to dynamically implement the new setpoint.
Example
With a DEFAULT value of 50 [N/s], it takes 20 [s] to build up 1000 [N] of tension on the material. The ramp function is launched with a starting value = 0, provided open and closed-loop tension-controlled operation are not active. The tensile force setpoint is diagnosed in the parameter Tension control - set tensile force.
0x5052:017
0x5052:017The setpoint torque from the tension control open loop is displayed in the parameter Tension control - set torque.
0x5052:024
0x5052:024The parameter Max. tension at dmax and rated motor torque serves as a guide to determine whether the maximum required web tension can be provided at maximum diameter and rated motor torque.
0x5052:023
0x5052:023
When designing the winder driver, a reserve must be provided for compensating for the friction and acceleration torque.
Tension-controlled (open-loop) operation is enabled by setting bit 18 in the parameter Control signals. 0x5050:010 Bit 18
The activated status is reported back in bit 18 of the parameter Status signals.
0x5050:110 Bit 18
Relevant parameters of other functions
|
Address
|
Name
|
Default setting
|
Setting range
|
|
External set tension
|
x.xx N (Read only)
|
||
|
Source of tension control influence
|
External [0]
|
Selection list
|
|
|
Set tension
|
4.00 N
|
0.00 ... 21474836.47 N
|
|
|
Set tensile force ramp
|
50.0000000000 N/s
|
0.0000000000 ... 2147483647.0000000000 N/s
|
|
|
Tension control - set tensile force
|
x.xx N (Read only)
|
||
|
Max. tension at dmax and rated motor torque
|
x.xx N (Read only)
|
||
|
Tension control - set torque
|
x.xxxx Nm (Read only)
|
||