Torque-based tension control open loop

In order to prevent sudden jumps, the tensile force setpoint is fed via a ramp generator. The ramp function is adapted to the time response via the parameter Set tensile force ramp in the application. 0x5052:010
The ramp must be adapted such that overly rapid setpoint value changes will not lead to instability, while still being sufficiently dynamic to dynamically implement the new setpoint.
 
Example
With a DEFAULT value of 50 [N/s], it takes 20 [s] to build up 1000 [N] of tension on the material. The ramp function is launched with a starting value = 0, provided open and closed-loop tension-controlled operation are not active. The tensile force setpoint is diagnosed in the parameter Tension control - set tensile force. 0x5052:017
The setpoint torque from the tension control open loop is displayed in the parameter Tension control - set torque. 0x5052:024
 
The parameter Max. tension at dmax and rated motor torque serves as a guide to determine whether the maximum required web tension can be provided at maximum diameter and rated motor torque. 0x5052:023
When designing the winder driver, a reserve must be provided for compensating for the friction and acceleration torque.
 
Tension-controlled (open-loop) operation is enabled by setting bit 18 in the parameter Control signals. 0x5050:010 Bit 18
The activated status is reported back in bit 18 of the parameter Status signals. 0x5050:110 Bit 18
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
External set tension
x.xx N (Read only)
Source of tension control influence
External [0]
Selection list
Set tension
4.00 N
0.00 ... 21474836.47 N
Set tensile force ramp
50.0000000000 N/s
0.0000000000 ... 2147483647.0000000000 N/s
Tension control - set tensile force
x.xx N (Read only)
Max. tension at dmax and rated motor torque
x.xx N (Read only)
Tension control - set torque
x.xxxx Nm (Read only)