Following error monitoring

The difference between setpoint and actual position describes the following error. Ideally, the following error should be "0". When the position control is set optimally, only a minimum following error is caused that is always compensated dynamically and not increases continuously.

Certain processes, however, require that a defined limit as a difference between set position and actual position is not exceeded. If it is exceeded, it may have been caused by mechanical blocking in the machine and the system part is not situated at the position defined at that time. In such a case, it makes sense to activate the "Fault" error response to make the motor torqueless.

The current following error is made available at the L_MC1P_AxisBasicControl .lrActFollowingError output and displayed in the ActFollowingError diagnostics parameter (subindex 57 ).

Note!

Following error monitoring system in the Servo Inverter i700

Following error monitoring (parameters 0x6066 ... 0x6068 of the i700 servo inverter) is not required in the FAST system. It is intended for evaluation by external control systems. In the FAST system, following error monitoring is executed on the Lenze control and is configured via the motion axis parameters (subindex 54 ... 59 ).

The following parameters serve to parameterise two independent following error monitoring systems:

Following error: Monitoring effective (subindex 54)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Activate following error monitoring system

Selection list (Lenze setting printed in bold)

Info

0

Deactivated

Not activated

1

Activated

Activated

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_8

Following error: Warning threshold (subindex 55)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Following error limit 1, warning threshold

Setting range (min. value | unit | max. value)

Lenze setting

0

Unit

2147483647

180 Unit

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Following error: Error threshold (subindex 56)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Following error limit 2, error threshold

Setting range (min. value | unit | max. value)

Lenze setting

0

Unit

2147483647

360 Unit

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Response - following error (subindex 59)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Response if following error limit 2 has been exceeded

Selection list (Lenze setting printed in bold)

Info

0

Reserved

2

Reserved

19

Error->Fast stop

Stopping is performed with the profile parameters ErrorStopDeceleration , see subindex 48 , and ErrorStopJerk , see subindex 49 .

20

Error->QSP

Stopping with the quick stop function of the inverter (0x6085).

21

Error->QSP->CINH

Stopping with the quick stop function of the inverter (0x6085). After reaching standstill, the inverter is locked.

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_16

Behaviour in case the following error monitoring system is active

The response for exceeding the following error limits is permanently set. If the following error limit 1 is exceeded:

  • The "FollowingError1" error message (error number 20502) is generated.
  • No change to the "ErrorStop" axis state takes place.

When following error limit 2 has been exceeded:

  • The "FollowingError2" error message (error number 20503) is generated.
  • If the axis is stopped as a function of the response set in subindex 59 ,
    see description in the subindex 59 selection list.
  • A change to the "ErrorStop" axis state takes place.
    The axis can only be traversed again after the error has been acknowledged via MC_Reset .