Brake control

Settings for controlling an optional holding brake.

Note!

Application-related control an status signals of the brake control are available via the FB L_MC1P_BrakeInterface .

Preconditions for an active brake control

When using the holding brake control of the Servo Inverter i700 by the Lenze control, the following conditions have to be fulfilled:

  • Setting in the drive: 0x2820:1 = 1 for control via the control word
  • Selection of the brake mode (subindex 110 : 1 or 2) in the motion axis
    • When the brake mode is changed (subindex 110 ), the associated object of the drive (0x2820:1) is automatically written to the associated value through the motion axis.
Manual holding brake control
  • Manual holding brake control (BrakeMode = 1, manual operation active)

The holding brake can be controlled directly via the L_MC1P_BrakeInterface FB , "xReleaseBrake" input.

In this operating mode, the following will not be affected:

  • Setting of the pulse inhibit (or controller inhibit) to the output signal.
  • All logic functions
Tip!

The mode can be used in order to easily check whether the holding brake switches correctly.

Automatic holding brake control

With Brake:OperationMode (subindex 110 = 2) the automatic motor holding brake control is active.

The behaviour of the motor holding brake control depends on whether the Servo-Inverter i700 is to enabled or inhibited via the MC_Power.bRegulatorOn control signal.

Control sequence for release / closing of the motor holding brake

Load magnetisation of the brake / feedforward control torque

Brake is released

Brake is closed

"Release motor holding brake" process

When MC_Power.bRegulatorOn = TRUE, the process for releasing the motor holding brake is automatically started:

  1. The Servo-Inverter i700 is enabled and the starting torque is for the torque feedforward control is specified.
  2. When the actual torque is = 0.9 x feedforward control torque
  • the motor holding brake is triggered for release ( xReleaseBrakeOut = TRUE)
  • the motor holding brake release time starts.
  1. After the motor holding brake release time has elapsed, the xBrakeReleased status is set to "TRUE". The motor holding brake is released and from now on the drive is able to perform movements.

"Close motor holding brake" process

Note!

The servo inverter will only be inhibited when the motor holding brake is closed.

Exception:

The motor holding brake is applied immediately if the Servo-Inverter i700 is inhibited via the safe-torque-off function (STO) or via fault response.

When MC_Power.bRegulatorOn = FALSE, the process for closing the motor holding brake is automatically started:

  1. The Servo-Inverter i700 remains enabled during the motor holding brake closing time.
  2. The xBrakeReleaseOut output is set to "FALSE" for closing the motor holding brake.
  3. The motor holding brake closing time is started.
  4. After the motor holding brake closing time has elapsed, the xBrakeReleased = FALSE status indicates that the motor holding brake is closed and the load has been transmitted. The servo inverter is inhibited.
Torque feedforward control

For a jerk-free transmission of the load, the required drive torque for releasing the motor holding brake can be pre-controlled.

  • The function is automatically effective if a starting torque has been selected.
  • The source of the starting torque can be defined via the subindex 117 .
  • Display of the effective feedforward control torque in subindex 115 .

The lrTorqueAdd input at the FB L_MC1P_BrakeInterface can be used to define an additive torque from the application for load compensation. The additive torque can either be a fixed standard value (subindex 118 ) or the automatically detected stopping value (display in subindex 114 ). The automatically detected stopping value is persistently saved in the control system. The stopping value is automatically deleted when the gearbox factors are changed or when the brake mode changes to Off .

Note!
  • A timeout monitoring serves to create the torque after magnetising the motor. If the torque does not reach at least 90% of the starting torque in one second, the monitoring system triggers an error "TimeOut torque feedforward control".
  • The FB L_MC1P_BrakeInterface provides interfaces for the application to release the brake or e.g. specify an additive starting torque. For executing a brake test or grinding in the brake, separate function blocks are available as well.

Brake operating mode (subindex 110)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Brake mode

Note: When the brake mode is changed, the associated object of the lower-level drive (0x2820:1) is automatically written to the associated value through the motion axis.

Selection list (Lenze setting printed in bold)

Info

0

Off (logic in the drive)

The holding brake logic in the control system is inactive. The holding brake logic of the lower-level drive is active (0x2820:1).

Note:

When the brake mode is changed from 1 or 2 to the setting 0, the 0x2820:1 object is automatically written to the value "0" (control via device status machine).

1

Manual release (PLC)

Manual release of the holding brake via the control ( L_MC1P_BrakeInterface ).

Setting in the drive: 0x2820:1 = 1

Note: If the brake is released with the setting 0x2820:1 ¹ 1, parameter 0x2820:1 is automatically set to the value "0" and the "InvalidBrakeState" error (error number 20532) is displayed.

2

Automatic brake logic (PLC)

0x2820:1 = 1

The automatic brake logic in the control system is active.

Setting in the drive: 0x2820:1 = 1

Note: If the brake is released with the setting 0x2820:1 ¹ 1, parameter 0x2820:1 is automatically set to the value "0" and the "InvalidBrakeState" error (error number 20532) is displayed.

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_32

Brake opening time (subindex 111)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Brake opening time

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0.100 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Brake closing time (subindex 112)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Brake closing time

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0.100 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Active brake operating mode(subindex 113)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Display of the activated brake mode

Selection list (read only; initialisation printed in bold)

0

Off (logic in the drive)

1

Manual release (PLC)

2

Automatic brake logic (PLC)

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_32

Brake : Saved torque (subindex 114)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Display of the saved holding torque (at the gearbox output end)

Display area (min. value | unit | max. value)

Initialization

Nm

0 Nm

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Brake: Active starting torque (subindex 115)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Display of the effective feedforward control torque (at the gearbox output end)

The effective feedforward control torque is the sum of the active feedforward control torque depending on the selected subindex 117 and the additional torque which is defined via the L_MC1P_BrakeInterface.lrTorqueAdd input.

Display area (min. value | unit | max. value)

Initialization

Nm

0 Nm

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Brake : Source of starting torque (subindex 117)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Source of starting torque 1

Selection list (Lenze setting printed in bold)

0

last stopping value

1

SubIndex 118

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_16

Brake : Starting torque (subindex 118)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Starting torque at the gearbox output end

Setting range (min. value | unit | max. value)

Lenze setting

Nm

0 Nm

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Brake : Acceleration time - feedforward control (subindex 119)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Acceleration time feedf. control

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Brake: Reference for acceleration time (subindex 120)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Reference to acceleration time

Selection list (Lenze setting printed in bold)

Info

0

Reference torque

Reference torque

1

Start torque

Torque setpoint

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_8