Limiter Interface

Functions are provided by the motion axis to support any available safety technology. Depending on which function of the safety module is requested, setpoint generation of the axis is automatically adjusted to prevent the safety technology from "responding".

The following function requests are supported by the axis:

  • Stop 1 and 2
  • Limited speeds 1 ... 4
  • Limited direction of rotation

The relevant control word of the safety component must be connected to the dwLimiterControl input of the L_MC1P_Limiter FB. If the safety technology is used in coupled axes, it may be necessary to respond to the requested function centrally rather than within the individual axes, e.g. via a virtual master. For this purpose, individual requests (grouped by function) can be excluded by the axis in subindex 162 so that they are not affected by the setpoint.

Limiter settings (subindex 162)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

SafetyInterface deactivation

  • Bit 0: reserved
  • Bit 1: ignore the SS1 request
  • Bit 2: ignore the SS2 request
  • Bit 3: ignore the SLS1-4 request
  • Bit 4: ignore the SDI request

Setting range (min. value | unit | max. value)

Lenze setting

0

4294967295

0

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_32

Current Limiter request (subindex 163)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Current SafetyInterface request

  • Bit 0: STO active
  • Bit 1: SS1 active
  • Bit 2: SS2 active
  • Bit 3: SOS active
  • Bit 4: SLS1 active
  • Bit 5: SLS2 active
  • Bit 6: SLS3 active
  • Bit 7: SLS4 active
  • Bit 8: SDIpos active
  • Bit 9: SDIneg active

Display area (min. value | unit | max. value)

Initialization

0

4294967295

0

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_32

Request: Limited stop 1
  • Diagnostics in subindex 163 bit 1
  • The drive is braked to a standstill with the quick stop deceleration ramp set in subindex 48 and subindex 49 .
  • The drive is then inhibited.
Request: Limited stop 2
  • Diagnostics in subindex 163 bit 2
  • The drive is braked to a standstill with the quick stop deceleration ramp set in subindex 48 and subindex 49 .
  • Afterwards, the drive remains in position control. Then bit 3 ("SOS") is set by the safety technology.
Request: Limited speed 1 ... 4
  • Diagnostics in subindex 163 bit 4 ... bit 7
  • If the current set speed or profile speed exceeds the pre-set value for the required limited speed (in subindex 150 , 152 , 154 , 156 ), the set speed of the configured delay time (in subindex 151 , 153 , 155 , 157 ) is reduced to the required limited speed.
    Exception : If the delay resulting from the parameters is smaller than the delay set in the motion profile, the system continues to decelerate to the SLS speed with the profile delay.
    Note : if no delay time is configured for the respective limited speed, this limited speed is inactive.
  • If several limited speeds are requested in parallel, the lowest speed is approached with the greatest deceleration.

The limited speeds and the permissible deceleration times can be configured in subindex 150 ... 157 :

Limited speed 1 (subindex 150)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Limited speed 1

Setting range (min. value | unit | max. value)

Lenze setting

0

Unit/s

2147483647

0 Unit/s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Deceleration time of limited speed 1 (subindex 151)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Deceleration time of limited speed 1

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Limited speed 2 (subindex 152)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Limited speed 2

Setting range (min. value | unit | max. value)

Lenze setting

0

Units/s

2147483647

0 Units/s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Deceleration time of limited speed 2 (subindex 153)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Deceleration time of limited speed 2

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Limited speed 3 (subindex 154)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Limited speed 3

Setting range (min. value | unit | max. value)

Lenze setting

0

Units/s

2147483647

0 Units/s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Deceleration time of limited speed 3 (subindex 155)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Deceleration time of limited speed 3

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Limited speed 4 (subindex 156)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Limited speed 4

Setting range (min. value | unit | max. value)

Lenze setting

0

Units/s

2147483647

0 Units/s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Deceleration time of limited speed 4 (subindex 157)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Deceleration time of limited speed 4

Setting range (min. value | unit | max. value)

Lenze setting

0

s

2147483647

0 s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Special cases

In the event of an active master/slave coupling (e.g. synchronism or cam profiler application), the speed is not normally reduced automatically because this should usually be implemented by the master axis.

However, if this is required, it can be activated via subindex 160 . In this case, the cyclically specified setpoints are also reduced to the limited speed. However, synchronism is no longer guaranteed.

An offset between the master and slave can be implemented automatically with the speed configured in subindex 159 once the limited speed request has been deactivated.

Compensating speed limited speed. (subindex 159)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Compensating speed if the "Limited speed" request has been cancelled.

Note: Only applies to followers if subindex 160 = 1

Setting range (min. value | unit | max. value)

Lenze setting

0

Unit/s

2147483647

0 Unit/s

Read access Write access Can only be changed in "Disabled" state No download

FLOAT_64

Follower SLS response (subindex 160)

Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

Limited speed in follower operation.

This function becomes effective if the following FBs are used:

  • by all technology modules following a cyclic master value.
  • Selection list (Lenze setting printed in bold)

    Info

    0

    Deactivated

    With subindex 160 = 1, the setpoints specified are limited to these if a "Limited speed" is activated.

    1

    Activated

    Read access Write access Can only be changed in "Disabled" state No download

    UNSIGNED_8

    Hard limitation of the SLS speed (subindex 161)

    Virtual axis 9400 HighLine i500 inverter i700 servo inverter i950 servo inverter Encoder

    "Hard" limitation of the speed controller setpoint to the limited speed requested.

    Selection list (Lenze setting printed in bold)

    Info

    0

    Deactivated

    In addition to limiting the setpoints, the speed controller input can also be limited to prevent an excessive increase in speed due to following error compensation.

    If a limited speed has been requested, the speed setpoint of the speed controller is hard limited after completion of the parametrised deceleration time. Index 0x2907:1 is automatically written to the requested limited speed. If index 0x2907:1 is not included in the mapping, write access is via SDO, otherwise directly into the mapped value.

    The default limit is changed in object 0x6080 if index 0x2907:1 is not supported by the device.

    1

    Activated

    Read access Write access Can only be changed in "Disabled" state No download

    UNSIGNED_8