Skewness monitoring

The skewness of the gantry axis can be monitored by the difference between the target position of the main axis and the following axis.

The skewness monitoring is only active if:

- it has been activated via subindex 60 (Skewness monitoring)

Calculation of the skewness in coupling mode “[1] Position absolute” or in coupling modes <>"[1] Position absolute" and known reference position:

∆p=pAct,Following pAct,Main-pOffset,Sub36

 

With

  • ∆p: current skewness;

  • pAct,Main: Actual position of main axis;

  • pAct,Following: Actual position of following axis,

  • pOffset,Sub36: Position offset between main and following axis, parameterizable in subindex 36

Calculation of the skewness in coupling mode “[1] Position relative” and unknown reference position:

∆p=pAct,Following-pAct,Main-pOffset,internal

With:

  • ∆p: current skewness;

  • pAct,Main: Actual position of main axis;

  • pAct,Following: Actual position of following axis,

  • pOffset,internal: Position offset between main and following axis, stored at controller enable

If the parameterizable warning threshold (subindex 61) or error threshold (subindex 62) is exceeded, the corresponding reaction (warning/error) can be triggered in the kinematics and in the coupled axes. The current skewness is given in subindex 63, the maximum skewness in subindex 64. The maximum skewness can be reset manually via bit 0 of the control word (subindex 8).