Tip |
|---|---|
|
The version of the function block as described here corresponds to the latest version of the function block in Version list of function blocks. |
SF_Antivalent is a certified PLCopen function block. For detailed information about applied standards, see "PLCopen – Technical Committee 5 – Safety Software".
|
Important |
|---|---|
|
The requirements listed in the standards must be fulfilled by the user. |
This function block links two antivalent SAFEBOOL inputs (NO/NC pair) to a SAFEBOOL output under discrepancy time monitoring. This FB should not be used stand-alone since it has no restart interlock. It is required to connect the output to other safety related functionalities.
Table 18. VAR_INPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Variable
Input for
|
|
|
|
|
Variable
Input for
|
|
|
|
|
Constant Maximum monitoring time for discrepancy state of both inputs The |
|
DiscrepancyTime |
|---|---|
|
For developers in Extended Level: The |
Table 19. VAR_OUTPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Safety-related output
|
|
|
|
|
|
|
|
|
|
|
Tip |
|---|---|
|
"Antivalent" means that during normal operation, the two inputs are in opposite states at the same time. This is sometimes called "complementary" or "non-equivalent". |
This function block processes two antivalent SAFEBOOL inputs to a SAFEBOOL output under discrepancy time monitoring. Both inputs are interdependent. The output of the function block shows the evaluation result of both channels.
If S_AntivalentOut = TRUE and one of the safety-oriented inputs changes, then the output immediately switches to FALSE.
Discrepancy time monitoring: The discrepancy time is the maximum time span in which both inputs may have the same state (this means that either both inputs are TRUE or both are FALSE) without the FB detecting an error. Discrepancy time monitoring starts when the status of an input changes. The function block detects an error when both inputs have the same values once the discrepancy time has elapsed.
The inputs must be switched symmetrically. This means that monitoring is performed both for switching the inputs to TRUE and FALSE.
Table 20. Logic table of inputs/outputs
|
Inputs |
Outputs |
||||||
|---|---|---|---|---|---|---|---|
|
|
|
|
|
|
|
|
|
|
|
|
|
Not started |
|
|
|
|
|
|
|
|
Not started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Not started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Not started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
|
|
|
Started |
|
|
|
|
|
Tip |
|---|---|
|
In the logic table, an arrow ( |
|
Tip |
|---|---|
|
Note: The transition from any state to the |
The S_AntivalentOut output is set to FALSE. Error is set to TRUE. DiagCode displays the error states. There is no Reset defined as an input coupled with the reset of an error. As soon as a Set of input values with the correct S_AntivalentOut is present, Error is FALSE again.
Table 21. FB-specific error codes
|
DiagCode |
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
Discrepancy time expired in status
|
|
|
|
Discrepancy time expired in status
|
|
|
|
Discrepancy time expired in status
|
Table 22. FB-specific status codes
|
DiagCode |
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
The function block is not active (basic state).
|
|
|
|
An activation has been detected by the block and the block is now activated.
|
|
|
|
The inputs are switched to active in the antivalent mode.
|
|
|
|
|
|
|
|
|
|
|
|
One channel has been switched to inactive; wait for the second channel to be switched to inactive as well.
|