Tip |
|---|---|
|
The version of the function block as described here corresponds to the latest version of the function block in Version list of function blocks. |
SF_OutControl is a certified PLCopen function block. For detailed information about applied standards, see "PLCopen – Technical Committee 5 – Safety Software".
|
Important |
|---|---|
|
The requirements listed in the standards must be fulfilled by the user. |
This function block controls a safety output with a signal of the standard controller and a safe signal with optional startup lock.
Table 76. VAR_INPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Variable Control signal of the upstream safety function block Typical function block signals of the library (for example:
|
|
|
|
|
Variable or constant Control signal of the standard controller
|
|
|
|
|
Constant Optional conditions for process control.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 77. VAR_OUTPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Controls the connected, safe devices or FBs.
|
|
|
|
|
|
|
|
WORD |
|
General:
The SF_OutControl FB is an output driver for a safety output.
The safety output is controlled via S_OutControl, which uses a signal from the standard controller (ProcessControl(BOOL) for process control) and a signal from the safety application (S_SafeControl (SAFEBOOL) for controlling the safety function).
Optional conditions for process control (ProcessControl):
-
An additional function start (
ProcessControl FALSE -> TRUE) is required, which follows the activation of the function block or the feedback of the safe signal (S_SafeControl). A staticTRUEsignal toProcessControldoes not setS_OutControltoTRUE. -
An additional function start (
ProcessControl FALSE -> TRUE) is not required, which follows the activation of the function block or the feedback of the safe signal (S_SafeControl). A staticTRUEsignal to ProcessControl setsS_OutControltoTRUEif the other conditions have been fulfilled.
Optional startup lock
-
Startup lock in the event of function block activation
-
Startup locks after interruption of the guard
|
Tip |
|---|---|
|
Note: The transition from any state to the |
|
Caution |
|---|---|
|
The |
The following conditions force a transition to the Error state:
-
Invalid static Reset signal in the process
-
Invalid static
ProcessControlsignal. -
ProcessControlandResetare incorrectly connected due to a program error.
In case of an error event, the S_OutControl output is set to FALSE and remains in this safe state. To exit the error states Reset Error, Init Error, or Lock Error, the Reset input has to be set to FALSE. To exit the Control Error error state, the ProcessControl input has to be set to FALSE.
After the transition from S_SafeControl to TRUE, the optional startup lock can be reset by a rising edge at the Reset input.
After function block activation, the optional startup inhibit can be reset by a rising edge at the Reset input.
|
Tip |
|---|---|
|
Note: The transition from any state to the |
Table 78. FB-specific error codes
|
|
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
Static
|
|
|
|
Static
|
|
|
|
Static signal at
|
|
|
|
Simultaneous rising trigger edge at
|
|
|
|
Simultaneous rising trigger edge at
|
Table 79. FB-specific status codes
|
|
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
The function block is not active (basic state).
|
|
|
|
Block activation startup lock is active. Reset required.
|
|
|
|
Triggered safety function
|
|
|
|
Safety function startup lock is active. Reset required.
|
|
|
|
Process monitoring is not active
|
|
|
|
Process monitoring is active and safety is activated.
|