Tip |
|---|---|
|
The version of the function block as described here corresponds to the latest version of the function block in Version list of function blocks. |
SF_TestableSafetySensor is a certified PLCopen function block. For detailed information about applied standards, see "PLCopen – Technical Committee 5 – Safety Software".
|
Important |
|---|---|
|
The requirements listed in the standards must be fulfilled by the user. |
This FB is used for periodic testing of a testable electronic/optical sensor or type 2 electro-sensitive protective equipment (ESPE). The FB can also be used for external testable safety sensors (ESPE: Electro-sensitive protective equipment, e.g. light beam). It also monitors the status of the safety sensor.
Table 49. VAR_INPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Variable Status of the sensor output, e.g. light grid.
|
|
|
|
|
Variable Input to start sensor test. Sets
|
|
|
|
|
Constant. Range: Test time for safety sensor. The 'TestTime' caution note must be observed. |
|
|
|
|
Constant Indicates whether external manual sensor test is supported.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TestTime |
|---|---|
|
For developers in Extended Level: The |
Table 50. VAR_OUTPUT
|
Name |
Data Type |
Initial Value |
Description, parameter values |
|---|---|---|---|
|
|
|
|
|
|
|
|
|
Safety-oriented output which displays the status of the ESPE.
|
|
|
|
|
Coupled with the test input of the sensor. Although specified as
|
|
|
|
|
Feedback signal to the process.
|
|
|
|
|
A positive signal edge indicates successful execution of the automatic sensor test.
|
|
|
|
|
|
|
|
|
|
|
Tip |
|---|---|
|
|
Type 2 ESPE is used for periodic testing. It is intended to detect a hazardous error (for example, sensor failure, response time exceeds the specified time). The test signal should simulate the operation of the measurement control and the duration of the periodic test should not exceed 150 ms. The test should verify that each light beam operates in the manner specified by the user. If the test should be initiated by an external, safety-oriented control system (e.g. a machine), then the ESPE should be equipped with suitable input equipment (e.g. terminal).
|
Important |
|---|---|
|
The |
It has to be monitored with a separate functionality that the test is initiated within appropriate intervals.
|
Caution |
|---|---|
|
The |
Test mode
-
StartTest = TRUE:STestOut = FALSE. Start of the monitoring time -
S_TestOutsignal stops the transmitter (monitoring ofTestTimestarted for the first time) -
S_OSSD_Inswitches fromTRUEtoFALSE(monitoring ofTestTimestarted for the second time) -
S_TestOutswitches fromFALSEtoTRUE -
Start transmitter
-
Sensor
S_OSSD_Inswitches fromFALSEtoTRUE -
Stop monitoring time
-
S_OSSD_OutisTRUEduring the test
Optional startup lock
-
Startup lock after activation of the FB
-
Startup lock after interruption of the guard
|
Tip |
|---|---|
|
Note: The transition from any state to the |
The following conditions force a transition to error status:
-
Test timeout without delayed sensor feedback
-
Test without sensor signal feedback
-
Invalid static Reset signal in the process
-
Plausibility check of the monitoring time setting
In case of an error event, the S_OSSD_Out output is set to FALSE and remains in this state. As soon as the error has been corrected and the sensor is in operation (S_OSSD_In = TRUE), a reset removes the error status and sets the S_OSSD_Out output to TRUE.
If S_AutoReset = FALSE, then a rising trigger edge is required at Reset.
After the transition from S_OSSD_In to TRUE, the optional startup lock can be restarted by a rising edge at the Reset input.
After function block activation, the optional startup lock can be restarted by a rising trigger edge at the Reset input.
Table 51. FB-specific error codes
|
|
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
Invalid value of the TestTime parameter Values between
|
|
|
|
Static Reset condition detected after FB activation
|
|
|
|
Static
|
|
|
|
Static reset condition detected in status
|
|
|
|
Static reset condition detected in status
|
|
|
|
Static reset condition detected in status
|
|
|
|
Static reset condition detected in status
|
|
|
|
Static reset condition detected in status
|
|
|
|
Test time expired in status
|
|
|
|
Test time expired in status
|
Table 52. FB-specific status codes
|
|
Statue Name |
Status description and output setting |
|---|---|---|
|
|
|
The function block is not active (basic state).
|
|
|
|
An activation was detected by the function block.
|
|
|
|
The FB has detected a safety requirement. The switch has not yet been tested automatically.
|
|
|
|
Wait for rising trigger edge after status
|
|
|
|
The automatic sensor test has failed. An external manual sensor test is necessary. Support for the necessary external manual sensor test has been activated on the function block ( A negative signal edge is required at the sensor.
|
|
|
|
The automatic sensor test has failed. An external manual sensor test is necessary. Support for the necessary external manual sensor test has been activated on the function block ( A
|
|
|
|
The automatic sensor test has failed. An external manual sensor test is necessary. Support for the necessary external manual sensor test has been activated on the function block ( The external manual test is complete. The device detected a complete sensor switching cycle (externally controlled).
|
|
|
|
The FB has not detected a safety requirement. The sensor was not tested automatically.
|
|
|
|
The automatic sensor test is active. Test Timer is started for the first time. The transmitter signal has been switched off by the function block. The signal of the receiver has to follow the signal of the transmitter.
|
|
|
|
The automatic sensor test is active. Test Timer is started for the second time. The transmitter signal of the sensor has been switched on by the function block. The signal of the receiver has to follow the signal of the transmitter.
|
|
|
|
The FB has not detected a safety requirement. The sensor was tested automatically.
|
|
|
|
The FB has detected a safety requirement. The switch was tested automatically.
|
|
|
|
Wait for a rising trigger edge of Reset after status
|